Fujitsu Airstage UTY-VGGXZ1 Installation Manual page 4

Network convertor
Hide thumbs Also See for Airstage UTY-VGGXZ1:
Table of Contents

Advertisement

Transmission
cable
Outdoor
unit
Indoor
unit
Wireless remote
controller
[Example of connecting group remote controllers in a parallel ar-
rangement]
Transmission Cable to
VRF System
FUSE (3 A)
1Ø 50/60 Hz
208-240 V
SWITCH
(Disconnect switch)
Power Supply
L1 + L2 + L3 + L4 + L5 + L6
[Example of connecting group remote controllers in series]
Terminal box
K K
K
RC UNIT
UNIT
L1 + L2 + L3 + L4 + L5 + L6 + L7
Note:
Use of a terminal box is recommended when a junction is made in the
wiring.
Do not bind the power cable, remote controller cable and transmission
cable to avoid an erroneous operation.
Use ground cable to ground the network convertor.
Use shield cable for transmission cable and remote controller cable.
The shield metal should be grounded.
Install the disconnect switch to the easily accessible location.
Install the fuse (3A) to the L line of power supply cable.
En-3
Remote controller
cable
Network
convertor
Wired remote
Group remote
controller
controller
Transmission Cable to
VRF System
K K
K
POWER
RC UNIT
UNIT
SUPPLY
NETWORK CONVERTOR
100 m (328 ft.)
or
100 m (328 ft.)
5. 1. 2.
Setting method when connecting a single split
indoor unit
[Example of connecting single split type
indoor unit in a parallel arrangement]
Case 1
Transmission Cable
Transmission Cable
FUSE (3 A)
1Ø 50/60 Hz
208-240 V
SWITCH
(Disconnect
switch)
POWER
SUPPLY
Power Supply
NETWORK CONVERTOR
Case 2
Wired remote controller
Transmission Cable
Transmission Cable
1Ø 50/60 Hz
FUSE (3 A)
208-240 V
SWITCH
(Disconnect
switch)
POWER
SUPPLY
Power Supply
NETWORK CONVERTOR
Note:
Install the disconnect switch to the easily accessible location.
Install the fuse (3A) to the L line of power supply cable.
*1.
Up to 16 indoor units may be controlled with a single network con-
vertor, however multiple indoor units connected to the network con-
vertor are generally required to have the same operation setting.
*2.
Always use indoor units with the same RC model or the same
system type when connecting multiple indoor units. Refer to "[DIP
switch - SW103 <1, 2, 3, 4>] RC model or system type setting" in "12
CIRCUIT BOARD SETTING" for information about RC models.
*3.
Connect a single big multi system to a single network convertor. 2
units or more of big multi systems cannot be connected. Big multi
system and single split system can also be connected simultane-
ously.
*4.
Network convertor is necessary for each indoor unit.
*5.
For using J series heat pump system, "AUTO" and "FAN" mode
should not be used.
*6.
When connecting the J-series heat pump model, the set opera-
tion conditions will be displayed on the control unit. Therefore, the
Indoor unit
Max. 16 units
K K
K
RC UNIT
UNIT
Indoor unit
Max. 2 units
Max. 16 units
K K
K
RC UNIT
UNIT
Single
Big Multi
Split