FusionModule2000 Smart Modular Data Center
Maintenance Guide
Figure 6-7 Testing the busbar energized or not
Step 8 Remove cables from the general input unit using a 13# socket wrench and a 6# hex key.
Issue 05 (2020-03-25)
While removing cables, clearly label the cables with its corresponding terminal ports for later
connection.