B Proposed Initial Setting
B.4 GT and Side Igniter Applications
Table B.4: Proposed Initial Settings for GT and Side Igniter Applications
(Continued)
Application Description
AC Amplitude
Function Set
Function Identifier
Intensity Pickup
Intensity Dropout
Intsensity Hi
Frequency Pickup
Frequency Dropout
Frequency Hi
AC Pickup
AC Dropout
AC Hi
Quality Norm Intensity
Quality Norm Intensity Hi
Quality Norm Frequency
Quality Norm Frequency Hi
Quality Norm AC
Quality Norm Frequency AC
Frequency Sensitivity
Intensity Smoothing
Frequency Smoothing
AC Smoothing
Delay on Dropout
Delay on Pickup
Maximum Frequency
8VZZ005286 B
Gas Turbine
Off
A
GT
5
5
5
5
20
20
55
0
0
0
125
Side Ignitor
Off
B
A
IGN
10
10
15
15
15
15
55
5
8
2
125