116 Maintenance
7.
Close the inlet valve (a) and outlet valve (located on the right-hand side of the
cubicle). Lead the drain hoses (b, on both sides of the cubicle) into a suitable
container. Open the drain valves (c, on both sides of the cubicle). This will drain
all modules in the cubicle.
c
a
8.
After the module has drained, disconnect the piping from the module.
b