8. Refrigerant Piping System
8.4 Pipe Connection Method/Precautions for Series connections
between Outside units
Separate Y branch joints are needed for series connections between outside units.
Y-branches between the outside units must be installed horizontally.
Please refer to the below connection examples to install pipe connections between outside units.
Pipe connection between outside units (General Case)
Pipes between outside units are 2 m(6.6 ft) or less
28
Heat Pump
Oil Trap
The maximum pipe length
after the first branching
between the outside unit is
10 m (33 ft) or less
2 m (6.6 ft) or less
Installation of Outside Units