Panasonic U-10MF1E8 Service Manual page 139

3-way system
Hide thumbs Also See for U-10MF1E8:
Table of Contents

Advertisement

4. 3-WAY Alarm Codes
L17 Alarm
Alarm code
L17
Alarm meaning
Outdoor unit model mismatch
Alarm conditions
This alarm occurs when a unit other than R410A refrigerant model is connected.
Probable cause
(1) A unit that uses R407C refrigerant, or a R22 model unit, was connected by mistake.
(2) The connected unit is correct, however the refrigerant type setting in the outdoor unit
EEPROM (item code 80) is incorrect.
Check
(1) Check the refrigerant type at the connected unit.
(2) Use the outdoor unit maintenance remote controller and check the item code 80 refrigerant
type. If the setting is incorrect, change it to R410A.
Correction
Example
Notes
The outdoor unit's maintenance remote controller is required in order to set the refrigerant type in
the outdoor unit EEPROM.
5 - 23