8.1 Important Information On Malfunction Procedures

• Boards should not be replaced due to ER-05, ER-07, ER-03, ER-15, ER-16, AE error codes.
• Please make sure that you do not replace the sensor without seeing an error code. Sensors on inverter products rarely break
down.
• Protection codes shown with LED on the outdoor unit do not indicate a malfunction; these are codes showing that the product
has entered the protection mode due to environmental conditions and external factors. When the conditions go back to normal,
the protection status of the product will also go away.
• The compressor does not operate by continuously increasing or decreasing its frequency. (For example, it rotates at a constant
frequency when the room temperature is equal to the set temperature.) Such situations should not be regarded as errors
• In the event of an ER-06 malfunction, first, apply the checking steps specified in the troubleshooting flow chart. If you cannot
solve the problem, finally perform the self-testing procedure.
• ,Each malfunction record entered can be seen by the technical personnel performing field track. In order to diagnose problems
more easily and faster and take action, to transfer more accurate information to the service providers, and to process invoices
properly, please make sure that the malfunction descriptions are understandable, informative and appropriate. If necessary, take
photographs and videos and include them in the records.
• Descriptions such as "Gas charge performed, problem solved." are not enough. Leakage check must be performed, and the
information regarding the place of the repair must be written, and photographs must be included when necessary. The part
repaired, such as "compressor, 4-way valve, condenser, etc." must be entered correctly.
• Remember to specify the error code received in case of electronic board replacement.

8.2 Error Codes

ERROR
Compressor cable disconnected / Sw compressor incompatibility
Indoor unit pipe sensor is on or short circuited
Indoor unit fan motor error
Indoor unit setting not performed/deleted
Indoor and outdoor unit communication error
Gas leak error
Current protection/sudden disconnection in supply
Model incompatibility between units
Board cooling sensor is on or short circuited
Compressor start protection
Compressor over current protection (if it occurs during operation)
Compressor over current protection (if it occurs during first start)
Outdoor environmental sensor is on or short circuited
Compressor pressing sensor is on or short circuited
Outdoor unit setting not performed/deleted
High voltage error during startup (card or reactor sourced)
Low/high voltage protection
Compressor discharge temperature is too high product stopped
(protection)
AC high voltage information
Board cooler temperature is too high, product stopped (protection)
Arc protection (loose connections)
Outdoor unit BLDC fan motor error
Indoor Unit
Outdoor Unit LED
Display
ER 02
Blinking 25 times - stopping for 3 sec.
ER 03
No display
ER 04
No display
ER 05
No display
ER 06
Blinking 9 times - stopping for 3 sec.
ER 07
Blinking 7 times - stopping for 3 sec.
No display
Blinking 8 times - stopping for 3 sec.
ER 09
Blinking 22 times - stopping for 3 sec.
ER 10
Blinking 15 times - stopping for 3 sec.
ER 11
Blinking 11 times - stopping for 3 sec.
ER 13
Blinking 13 times - stopping for 3 sec.
ER 14
Blinking 8/13 times - stopping for 3 sec.
ER 15
Blinking 16 times - stopping for 3 sec.
ER 16
Blinking 17 times - stopping for 3 sec.
ER 18
No display
ER 17
No display
HL
Blinking 18 times - stopping for 3 sec.
No display
Blinking 19 times - stopping for 3 sec.
No display
Blinking 20 times - stopping for 3 sec.
No display
Blinking 21 times - stopping for 3 sec.
AE
Blinking 24 times - stopping for 3 sec.
ER26
Blinking 26 times - stopping for 3 sec.
28