Comm
Title
unicati
on No.
c021
C021
Scanner output 1 address
c022
C022
Scanner output 2 address
c023
C023
Scanner output 3 address
c024
C024
Scanner output 4 address
c025
C025
Scanner output 5 address
c026
C026
Scanner output 6 address
Communication error
c100
C100
detection delay time
Inverter operation at the
c101
C101
communication loss action
Preset speed
c102
C102
operation selection
Communication time-out
c103
C103
condition selection
Function
0: None
1: fd01 (Inverter status 1)
2: fd00 (Output frequency, 0.01Hz)
3: fd03 (Output current, 0.01%)
4: fd05 (Output voltage, 0.01%)
5: fc91 (Inverter alarm)
6: fd22 (PID feedback value, 0.01Hz)
7: fd06 (Input terminal status)
8: fd07 (Output terminal status)
9: fe36 (VIB input, 0.01%) / fe35 (RR input) [VF-AS3] *
10: fe35 (VIA input, 0.01%) / fe36 (RX input) [VF-AS3] *
11: fe37 (VIC input, 0.01%) / fe37 (II input) [VF-AS3] *
12: fd04 (Input voltage (DC detection), 0.01%)
13: fd16 (Estimated speed (real-time value), 0.01Hz)
14: fd18 (Torque, 0.01%)
15: fe60 (My monitor 1) [VF-AS3] *
16: fe61 (My monitor 2) [VF-AS3] *
17: fe62 (My monitor 3) [VF-AS3] *
18: fe63 (My monitor 4) [VF-AS3] *
19: f880 (Free notes)
20: fd29 (Input power, 0.01kW)
21: fd30 (Output power, 0.01kW)
22: fe14 (Cumulative operation time, 0.01 = 1 hour)
23: fe40 (FM terminal output monitor, 0.01%)
24: fe41 (AM terminal output monitor) [VF-AS3] *
25: fd20 (Torque current, 0.01%)
26: fd23 (Motor overload factor, 0.01%)
27: fd24 (Drive overload factor, 0.01%)
28: fd25 (PBR overload factor, %)
29: fd26 (Motor load factor, %)
30: fd27 (Drive load factor, %)
31: fe56 (Pulse train input, pps)
32: fe70 (Drive rated current, 0.1A)
33: fe76 (Input Watt-hour, 1kWh  10
34: fe77 (Output Watt-hour, 1kWh  10
35: fd83 (IGBT temperature, degree C)
100: ETA
101: RFRD
0-101 (Same as c021)
0-101 (Same as c021)
0-101 (Same as c021)
0-101 (Same as c021)
0-101 (Same as c021)
0.0 - 100.0 sec.
0: Stop and controlled by cmod, fmod
1: Operation continue
2: Deceleration stop
3: Coast stop
4: Network error stop (err8 trip)
5: Preset speed operation (by c102 setting)
0: None
1 to 15: Preset speed
0: Disconnection detection
1: When communication mode enable (Both cmod and
fmod are set CANopen or communication option)
only
2: 1 + Driving operation
Description
- 16 -
E6581818⑭
4
4
4
4
4
4
4
4
f749
)
f749
)
Default
2
100*
2
101*
2
0*
2
0*
2
0*
2
0*
0.0sec
4
0
0