Hitachi Relion RES670 Commissioning Manual page 118

Phasor measurement unit
Hide thumbs Also See for Relion RES670:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
Take the set characteristic into consideration, see Figure
5.
Measure the trip time of the timer by injecting a current two times the set INcosPhiPU value and the
polarizing voltage 1.2 · VNRelPU.
Tinv
ANSI13000294 V1 EN-US
6.
Compare the result with the expected value.
The expected value depends on whether definite or inverse time was selected.
7.
Set the polarizing voltage to zero and increase until the boolean output signal UNREL is activated,
which is visible in the Application Configuration in PCM600 when the IED is in online mode.
Compare the voltage with the set value VNRelPU .
8.
Continue to test another function or complete the test by setting the test mode to Disabled.
ANSI06000650 V3 EN-US
Figure 28:
112
TDSN SRef
=
( )
3
3
cos ϕ
I
V
0
0
test
Characteristic with ROADir restriction
© 2017 - 2022 Hitachi Energy. All rights reserved
28
 0
RCADir
3I
0
Trip area
3 
I
cos
0
ROADir
ANSI06000650-3-en.vsd
1MRK 511 409-UUS Rev. K
and Figure 29.
3
V
V
0
ref
Phasor measurement unit RES670
Commissioning manual
(Equation 77)