Bay control REC670 2.1 IEC
Differential protection
Table 28. High impedance differential protection, single phase HZPDIF
Function
Operate voltage
Reset ratio
Maximum continuous power
Operate time at 0 to 10 x U
Reset time at 10 x U
to 0
d
Critical impulse time
Operate time at 0 to 2 x U
Reset time at 2 x U
to 0
d
Critical impulse time
ABB
Range or value
(10-900) V
I=U/R
>95% at (30-900) V
2
U>Trip
/SeriesResistor ≤200 W
Min. = 5 ms
d
Max. = 15 ms
Min. = 75 ms
Max. = 95 ms
2 ms typically at 0 to 10 x U
Min. = 25 ms
d
Max. = 35 ms
Min. = 50 ms
Max. = 70 ms
15 ms typically at 0 to 2 x U
M13081-1 v12
d
d
1MRK 511 361-BEN D
Accuracy
±1.0% of I
at I ≤ I
r
r
±1.0% of I at I > I
r
-
-
-
-
53