Operating Instructions 03/2010

Advertisement

Table of Contents
loading

Summary of Contents for Siemens US-100-1

  • Page 1 US-100-1 US-100-3 Operating Instructions 03/2010...
  • Page 2: European Authorized Representative

    The user is responsible for all changes and repairs made to the device by the user or the user’s agent. • All new components are to be provided by Siemens Milltronics Process Instruments Inc. • Restrict repair to faulty components only.
  • Page 3: Installation

    Introduction Notes: • This product is intended for use in industrial areas. Operation of this equipment in a residential area may cause interference to several frequency based communications. • The Probe is to be used only in the manner outlined in this instruction manual. The Probe is an ultrasonic level monitor combining sensor and electronics in a single package.
  • Page 4: Flange Adapter (Optional)

    Mounting Mount The Probe so that the face of the sensor is at least 25 cm above the highest Note: anticipated level. Threaded hinged lid 7 mm The Probe is available in three thread types: 84 mm (0.3") (3.3") max. 2"...
  • Page 5 Operation Start Up program mode alphanumeric • With The Probe correctly installed (or ’20’ key aimed at a wall 0.25 to 5m [US-100-1], 0,25 to 8m [US-100-3]away), apply power. units • The Probe starts up displaying the ’4’ key following:...
  • Page 6: Calibration: Reference Method

    Calibration The calibration of the mA output may be done such that its span will be either proportional or inversely proportional to the material level. The 4 and 20 mA levels may be calibrated in Note: any order. proportional span inversely proportional span high level = 20 mA high level = 4 mA...
  • Page 7: Calibration, Scrolling Method

    Adjustments There are several operating adjustments that can be made to The Probe. • Press the "4" and "20" keys simultaneously until the desired adjustment is obtained. A viewing sequence of the stored value is automatically initiated. • During this time, press either the "4" or "20" key to change the value. After viewing or changing, operation automatically reverts to the Run mode (6 sec).
  • Page 8: Speed Of Response

    Blanking The Probe Blanking is used to ignore the zone in front of the transducer where false echoes are at a level that blanking interfere with the processing of the true echo. It is measured outward from the sensor face. The minimum recommended blanking value is 0.25 m (0.82 ft) but can be increased in order to extend the blanking.
  • Page 9 • To change the speed of response, obtain the `SP' display. • Scroll forward through the options (1-2-3) by pressing the "20" key. Scroll backward through the options (3-2-1) by pressing the "4" key. • When the desired option is displayed, stop pressing the key. The display will automatically return to the Run mode (6 sec).
  • Page 10: Fail-Safe Timer

    • To change the fail-safe default obtain the `FLS' display. • Scroll forward through the options (1-2-3) by pressing the "20" key. Scroll backward through the options (3-2-1) by pressing the "4" key. • When the desired option is displayed, stop pressing the key. The display will automatically return to the Run mode (6 sec).
  • Page 11: Troubleshooting

    Supplement Loading vs. Supply Voltage Troubleshooting The echo is not reliable and The Probe is waiting for a valid echo before updating the measurement. Probable causes are: • material or object in contact with sensor face • The Probe is too close to the fill point •...
  • Page 12: Specifications

    Specifications Power: • 18 to 30 V DC, 0.2 A max Environmental: • location: indoor / outdoor • altitude: 2000 m max. • ambient continuous:-40 to +60 °C (-40 to +140 °F) temperature -20 °C (-5 °F) if metal mounting •...