Fujitsu AOYR14LCL Service Instruction page 40

Wall mounted type inverter, refrigerant r410a, indoor/outdoor unit
Table of Contents

Advertisement

(3). ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger
temperature sensor detects the temperature lower than Temperature .
Then, the anti-freezing control is released when it becomes higher than Temperature .
(Table 19 : Anti-freezing Protection Operation / Release Temperature)
A-D
E,F
(4). COOLING PRESSURE OVERRISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to temperature
compressor is stopped and trouble display is performed.
(Table 20 : Cooling Pressure Over Rise Protection Function Temperature)
ASYA07/09/12/14/18LCC
ASYB09/12LDC
(5). HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the
detection value of the indoor heat exchanger temperature sensor.
[ Control System ]
Indoor heat exchange
temperature
Temperature
The compressor frequency is
precisely controlled so that
it does not exceeds Temperature .
Temperature
It returns to the normal operation
Compressor Operation
[ ASYA07/12LCC, ASYB09/12LDC ]
46Hz or greater
45Hz
Frequency down every 120 sec
39 45Hz
26 38Hz
25Hz
18 25Hz
OFF
Temperature
Temperature
4°C
7°C
4°C
13°C
Temperature
67°C
67°C
Refer to below
ASYA07/09/12/14/18LCC 55°C
ASYB09/12LDC
Temperature
Temperature
[ ASYA14/18LCC ]
39Hz or greater
38Hz
Frequency down every 120 sec
30
38Hz
19 29Hz
18Hz
18Hz
OFF
05-18
or greater, the
Temp Temp Temp
Temp
53°C
52°C
50°C
55°C
53°C
52°C
50°C