Download Print this page
Siemens SIMATIC FDE Equipment Manual
Siemens SIMATIC FDE Equipment Manual

Siemens SIMATIC FDE Equipment Manual

Hide thumbs Also See for SIMATIC FDE:

Advertisement

Quick Links

SIMATIC FDE Gateway V1
FDE
SIMATIC FDE Gateway V1
Equipment Manual
05/2023
A5E52683268-AB
Preface
Siemens Industry Online
Support
Introduction
Overview of the technical
documentation
Installing and connecting a
device
Software and
commissioning
Certificates and approvals
Directives and declarations
Technical specifications
Dimension drawings
1
2
3
4
5
6
7
8
9
A

Advertisement

loading

Summary of Contents for Siemens SIMATIC FDE

  • Page 1 SIMATIC FDE Gateway V1 Preface Siemens Industry Online Support Introduction Overview of the technical documentation SIMATIC FDE Gateway V1 Installing and connecting a device Software and commissioning Equipment Manual Certificates and approvals Directives and declarations Technical specifications Dimension drawings 05/2023...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3 Table of contents Preface ..............................5 Siemens Industry Online Support ......................6 Introduction ............................7 Security information ......................7 IT security on the northbound side ..................7 IT security on the southbound side ..................8 Personal data ........................8 Overview of the technical documentation .................... 9 SIMATIC products .........................
  • Page 4 Electromagnetic Compatibility industrial area +A1:2011 ............. 56 ESD guideline ........................56 Technical specifications ........................59 General technical specifications ..................59 Ambient conditions ......................62 Dimension drawings ..........................63 Dimension drawings ......................63 SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 5 A prerequisite for understanding this manual is knowledge of how to use a PC. Basic knowledge of automation technology as well as IoT technologies is also recommended. Scope of this document These operating instructions apply to the SIMATIC FDE Gateway device. MLFB: 6ES7617-0BA01-0AB0 FDE conventions...
  • Page 6 For answers and solutions concerning automation technology. • mySupport Your personal working area in Industry Online Support for messages, support queries, and configurable documents. This information is provided by the Siemens Industry Online Support in the Internet (https://support.industry.siemens.com). SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 7 Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
  • Page 8 Make sure to protect the southbound connection in accordance with currently recognized security guidelines. This prevents spying on the field data. More information and application notes can be found here: (https://www.siemens.com/industrialsecurity) Personal data During the configuration of the FDE gateway, it is possible to store user-specific data such as certificates, usernames, and access passwords.
  • Page 9 For more documents on other hardware or specific information, please visit SIEMENS SiePortal. (https://sieportal.siemens.com/) SIMATIC products You can find an overview of the SIMATIC documentation available in Siemens Industry Online Support here: Industry Online Support International (https://support.industry.siemens.com/cs/ww/en/view/109742705)
  • Page 10 Parameter list The parameter list (https://support.industry.siemens.com/cs/ww/en/view/23708204) contains a detailed description of all parameters, ordered by function. It also contains a series of function charts as well as error and alarm messages.
  • Page 11 Overview of the technical documentation 4.3 SENTRON products SENTRON products SIMATIC FDE Gateway enables connection to the following measuring instruments: • SENTRON Modbus TCP PAC2200 • SENTRON Modbus TCP PAC3220 • SENTRON Modbus TCP PAC4200 The connection is established via X2 P1.
  • Page 12 Installing and connecting a device Scope of supply Supplied components The following components are included in the scope of supply of the SIMATIC FDE Gateway with article number 6ES7617-0BA01-0AB0: • 1 x complete unit SIMATIC FDE Gateway • 1 x 14-pin connection terminal X4...
  • Page 13 • Browser-based user interface for configuration and for viewing the device configuration • Forwarding of "southbound signals" via MQTT to northbound connectivity. Note The SIMATIC FDE Gateway cannot check the data integrity of southbound interfaces. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 14 • CE conformity • Easy installation and configuration • Cloud/IoT interface (MQTT 3.1.1) – Secure MQTT via TLS – Open data format (JSON payload) • ISO degree of protection IP20 according to IEC 60529 SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 15 Installing and connecting a device 5.4 Device design Device design The following figure shows the design of the SIMATIC FDE Gateway, with interfaces: ① Socket for connecting a WLAN or BLE antenna ⑤ LED display ② Ethernet interface X1 P1: TCP/IP interface ⑥...
  • Page 16 • Digital input 0 - 28.8 V DC, Type III input (pins 4-3 of the X4 plug) • Digital output 24 V DC, 300 mA (pins 11-12 of the X4 plug) The functionality depends on the configuration in the web server. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 17 300 mA For signal "0" 0 V - 5 V For signal "1" 12 V - 24 V For connection to I/O, see section "Connecting interfaces to connecting terminal X4 (Page 25)". SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 18 Operating modes and LED display Operating mode Color of SYS LED Illuminated green CONFIGURATION Orange flashing LED signaling SIMATIC FDE Gateway features 10 signal LEDs visible to the user. The LED display signals the following operating modes: Designa- LED name Operating Meaning tion...
  • Page 19 Do not dispose of the original packaging. Be sure to pack the device during transport and storage. 4. Check the contents of the packaging and the accessories for completeness and damage. Scope of delivery: – Device – DC connection terminal (plugged into the device). SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 20 Do not expose the device to direct heat radiation from a heater. If condensation occurs, wait about 12 hours or until the device is completely dry before switching it on. 6. Make a note of the device's identification data. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 21 Mounting instructions • The device is only approved for operation indoors. • When installing in a control cabinet, observe the SIMATIC installation guidelines (https://support.industry.siemens.com/cs/ww/en/view/1064706) as well as the relevant DIN/VDE regulations or the respective country-specific regulations. Secure mounting Open device must be installed in a cabinet or appropriate enclosure. The device is mounted on horizontal or vertical DIN rails with 35 mm DIN.
  • Page 22 2. Swivel the rail clamp of the device from below over the DIN rail. 3. Press the device towards the DIN rail. Press the DIN rail clamp in so that the device is firmly seated on the rail. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 23 1. Use a slotted screwdriver to pull the lower DIN rail clamp on the back of the device down to the extended position. This will release the unit from the rail. 2. Swivel the device away from the DIN rail. 3. Move the device upward and remove it. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 24 Regenerative feedback of voltage to ground by a connected or installed component can damage the device. Connected or installed peripherals must not introduce any voltage into the device. Regenerative feedback is generally not permitted. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 25 1. Switch off the power supply. 2. Identify the connections of the interface to be connected. 3. Connect all cables to the correct terminal sockets 4. Plug the connector in. 5. Switch on the power supply unit. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 26 To ensure strain relief, use cable ties or cable clamps to secure the connected cables to suitable fixing elements. Make sure that the cables are not pinched by cable ties or cable clamps. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 27 Connecting a device to the RS232 interface Connect the device to pins 5-8 of the X4 terminal. You can connect a SIMATIC FDE Gateway to one of the following converters via the RS232 interface on the converter-specific module or control device: •...
  • Page 28 5.10 Connecting the device Wiring example The following example from the SINAMICS G120 series shows the wiring between the converter and the SIMATIC FDE Gateway. Cable shield grounding: RS232 serial cable should be shielded. The shield should be connected to functional grounding at one end of the cable at least.
  • Page 29 Use the last 6 digits of the WiFi MAC address ② for the SSID: SSID = fde_gateway_[last 6 digits of the WiFi MAC address] Use the SSID with the underscores replaced by hyphens as the host name. Use the serial number ① as the password. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 30 Click "Sign up". After successful registration, you can connect to the device using your password. If the password is lost, the device has to be reset and reconfigured. Device configuration Log on to the device by entering your password: The start page appears. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 31 There are three icons in the top bar of the application: Use the icon to activate Dark mode. You can find the user information below the icon. Switch the language with the icon. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 32 – Fill in the "IP address" field with the address for ETH1 (X1). – Complete the fields "Subnet mask", "Gateway" and "DNS". – Save the configuration by clicking the "Save" button in the upper right corner. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 33 Host Configuration Protocol). – Move the switch to the "On" position. – Save the configuration by clicking the "Save" button in the upper right corner. Note The settings are only applied after a restart. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 34 Switch on the WLAN connection and fill in the parameters "Network name (SSID)" and "Password" for the WLAN connection. Complete the settings for the Wi-Fi client. Select a Wi-Fi network with good signal strength. During operation, the connection to a cloud/Internet connection can be set. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 35 Software and commissioning 6.4 Connectivity settings Connectivity settings You can set the following parameters under Connectivity: • MQTT parameters • Analog or digital input and digital output • USS parameters • Modbus TCP (X2) SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 36 • Subscribe topic name: Payloads in JSON format can be sent to the FDE via this topic • Endpoint: The address of the MQTT broker • Port: The port of the MQTT broker • Server CA certificate: Public certificate from the Certificate Authority (ca.crt) SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 37 1 second. All other times are adjustable, e.g. 5 s, 10 s, etc. You can find more examples of payloads with parameters in the section MQTT payload examples (Page 44). SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 38 Click "Add parameter". A parameter with name, data type, number, and index can then be inserted. Added and activated parameters are read out via USS. Deactivate the check box in the corresponding line to disable the parameter. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 39 Select the desired measurement type (current 0 - 20 mA or voltage 0 - 10 V). Activate digital input Set the switch to "On". Enter the signal name. Activate digital output Set the switch to "On". Select the desired initial port state (closed or open). SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 40 Settings of the Digital_Output application via MQTT protocol A Subscribe topic name is assigned under Connectivity/MQTT. Under this topic, you can change the values of the DIGITAL_OUTPUT application, e.g.: Publish desired changes to the application DIGITAL_OUTPUT: SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 41 The publish topic name must match the previously set subscribe topic name in the SIMATIC FDE Gateway. The following payload in the JSON format shows how the settings can be changed: "app": "DIGITAL_OUTPUT", "version": "1.0", "parameters": { "VALUE": true The VALUE value can be changed. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 42 Enable Modbus TCP connectivity and set the parameters in the Modbus TCP (X2) tab. Adding and activating parameters Click "Add parameter". A parameter with name, address, function code and arguments can then be inserted. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 43 Alternatively, you can select the parameters from the template. Select the check box in the corresponding line to enable the parameter. Deactivate the check box in the corresponding line to disable the parameter. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 44 "parameters": { "Parameter1": { "value": 315.854, "type": "float" "STATUS": { "value": 0, "type": "int32_t" "STATUS_INFO": { "value": "{}", "type": "string" "TIMESTAMP_MS": { "value": "1663312002231", "type": "string" "READOUT_MS": { "value": 35, "type": "uint32_t" SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 45 "type": "string" "VALUE": { "value": 1, "type": "int8_t" Explanation The value under "VALUE" corresponds to the state of the digital input: • Value: 1: Input voltage. • Value: 0: No input voltage. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 46 "value": "analog_input_voltage", "type": "string" "RAW_VALUE": { "value": 4057, "type": "uint32_t" "MA_VALUE": { "value": 20, "type": "float" "MV_VALUE": { "value": 0, "type": "float" Explanation The value under "MA_VALUE" is output directly in mA. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 47 "RAW_VALUE": { "value": 451, "type": "uint32_t" "MA_VALUE": { "value": 0, "type": "float" "MV_VALUE": { "value": 8185.19, "type": "float" "app": "USS", "parameters": { Explanation The value under "MV_VALUE" is entered directly in mV SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 48 Date and time settings Date & time The time configured on the device always corresponds to UTC as the primary format. This time can be selected manually or applied from the web browser: SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 49 If you forget the password, it can be reset by restoring the factory settings. To do this, use the "RESET" button. System upgrade If needed, you can find updated software versions in the SiePortal (https://sieportal.siemens.com/). You can update the software via the system upgrade interface: SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 50 • Ensure that the device is connected to a stable 24 V power supply. • Do not close or refresh the website. • Ensure that your client is always connected to the SIMATIC FDE Gateway hotspot. Do not leave the area.
  • Page 51 (only valid for G120). • The BFC Gateway settings and installation are described in the BFCG Function Manual (https://support.industry.siemens.com/cs/us/en/view/109801700). • Middleware script must be inserted (internal mapping of the parameter values). SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 52 These apps offer solutions for visualizing data and machine tool-related KPIs which provide information about the production and machine states. The Siemens Industrial Edge Hub platform also offers many pre-built apps. For example, the apps "Analyze MyDrives /Edge" or "Predictive Service Analyzer - Converter" were developed for monitoring the drive train.
  • Page 53 6.10 Settings for operation in MindSphere The Siemens IoT-as-a-service solution MindSphere saves operating data and makes them accessible through digital applications so that you can make decisions on the basis of valuable factual information. One of these apps is the Predictive Service Assistance app, which offers access via your tenant to all relevant service and asset data of the drive systems, such as pumps and fans.
  • Page 54 • Radio Equipment Regulations 2017 (RED) • Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations 2012 (RoHS). SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 55 DI FA TI COS TT P.O. Box 1963 D-92209 Amberg The UK Declaration of Conformity is also available for download from the Siemens Industry Online Support website under the keyword "Declaration of Conformity". RCM Declaration of Conformity for Australia/New Zealand FDE Gateway fulfills the requirements of the standard IEC 61000-6-4.
  • Page 56 The following abbreviations are commonly used for "electrostatic sensitive devices": • ESD - Electrostatic-sensitive device • ESD – Electrostatic Sensitive Device is the common international designation Electrostatic-sensitive devices can be labelled with the corresponding icon. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 57 These values correspond to the specifications of IEC 61000-4-2. ① Synthetic material ② Wool ③ Antistatic material such as wood or concrete SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 58 In this way, the discharge energy does not reach and damage any sensitive components. – Discharge your body electrostatically before taking module measurements by touching grounded metallic objects. Only use grounded measuring devices. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 59 Digital inputs Number of inputs Cable length (unshielded) Max. 600 m Input voltage • Type of input voltage < 5 V • "0" signal > 12 V • "1" signal SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 60 TCP/IP, DHCP, MQTT, Modbus TCP (X2) RS232 USS protocol Wi-Fi 2.4 GHz for configuration 2.4/5 GHz for northbound connection For unambiguous labeling, the LAN interfaces are numbered on the enclosure. The operating system numbering may differ. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 61 • 1 to 3 GHz: 70 dB (μV/m) P; 50 dB (μV/m) A (3 m distance) • 3 to 6 GHz: 74 dB (μV/m) P; 54 dB (μV/m) A (3 m distance) SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 62 5 … 8.4 Hz: Deflection 3.5 mm • 8.4 … 500 Hz: Acceleration 9.8 m/s Shock resistance, tested according to IEC 60068-2-27 150 m/s , 11 ms • Operation 250 m/s , 6 ms • Transport/storage SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...
  • Page 63 Dimension drawings Dimension drawings Dimensional drawing of the device All dimensions are in mm. Dimension drawing of the 14-pin X4 terminal The grid dimension is 2.54 mm. All dimensions are in mm. SIMATIC FDE Gateway V1 Equipment Manual, 05/2023, A5E52683268-AB...