7. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the Table 9.
(Table 9 : Compressor Operation Frequency Range)
AOU18RLXFZ
AOU24RLXFZ
AOU36RLXFZ
2. OPERATION FREQUENCY CONTROL AT START UP
For
AOU18RLXFZ / AOU24RLXFZ
The compressor frequency soon after the start-up is controlled as shown in the figure 13-1.
(Fig.13-1 : Compressor Control at Start-up)
85rps
56rps
40rps
For
AOU36RLXFZ
The compressor frequency soon after the start-up is controlled as shown in Figure 13-2.
(Fig.13-2 : Compressor Control at Start-up)
56rps
40rps
40rps
Cooling
Min
Max
20rps
100rps
20rps
90rps
60 - 780sec
120sec
180 - 900sec
60 - 720sec
180sec
Heating
Min
Max
24rps
110rps
20rps
95rps
120sec
300 - 1020sec
120sec
240 - 900sec
360 - 1020sec