8 System Power/Size

Max. AH
Power
Current
Capacity
Primary
5A (CPS-24
N/A
(Power
Power
Supply)
Supply);
or
2.5A (CPS-
24E Power
Supply)
Secondary
7.4A
200AH
(backup)
Accessories/Subassemblies/Networked panels
Monitor and Control Modules
Detectors
Signaling Line Circuits (SLC)
NFS2-640 Fire Alarm Control Panel
9 Operating Instructions
Frame and mount the NFS2-640 Operating Instructions, P/N 52744, adjacent to the control panel. See the back of this manual.
40
Derating Factor
N/A
26 AH batteries:
UL=1.2, ULC=1.5
55 AH batteries:
UL=1.2, ULC=1.8
100 AH batteries: UL=1.2, ULC=2.5
200 AH batteries: UL=1.2, ULC=2.5
Table 13 System Power
High-Speed Noti•Fire•Net - 200 Nodes
Noti•Fire•Net - 103 Nodes. 54 nodes when DVC is used in network paging.
Table 14 System Size
Max. Standby
Max. Alarm
Current
Current
891 mA (CPS-24)
2.4 A (CPS-24)
or
or
498 mA (CPS-24E)
1.46 A (CPS-24E)
4.4A
7.4A
(For 26AH batteries:
(max alarm
max standby current
current cannot
cannot exceed 0.65A)
exceed 6.75A.)
Maximum System Capacity
318
318
2
NFS2-640 UL Listing Document — P/N 52741LD:H9 5/19/2022
Max. Standby
Max. Alarm Duration
Time
N/A
N/A
24 hours
5 minutes standard,
15 minutes for
emergency voice/alarm
communications
systems.