PN 292-118
UL, FCC, IC, CE MARK, CCC
Approvals
Current consumption is determined using the following
formula: 30mA + (n × 20mA) where 30mA is the current
consumption of the logic board and n= the number of
actuated relays.
Table 5. Current Consumption
Configuration
All relays actuated
130mA
Note: Current consumption values of the X47 with actuated
relays should be deducted from class-2 output power rating in
Table 3 in order not to overdrive the power supply. The X47
should not be used to provide more than 70mA of external
class-2 power.
Maximum Load (including
logic board)