Apparent Power Control On The Inverter Output Side - Huawei 01075345 User Manual

Hide thumbs Also See for 01075345:
Table of Contents

Advertisement

SUN2000-(2KTL-6KTL)-L1
User Manual
Parameter Name
Shutdown
Shutdown at high feed-in power
at high
feed-in
a
power
Upper feed-in power threshold for inverter
shutdown (kW)
High feed-in power duration threshold for
triggering inverter shutdown (s)
Note a: This parameter is supported only for the AS4777 grid code.
----End

7.2.1.2 Apparent Power Control on the Inverter Output Side

On the home screen, tap Settings > Power adjustment to set inverter
parameters.
Issue 10 (2023-02-13)
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interaction
Description
● The default value is Disable.
● If this parameter is set to Enable,
the inverter shuts down for
protection when the grid-
connection point power exceeds
the threshold and remains in this
condition for the specified time
threshold.
● The default value is 0. This
parameter specifies the power
threshold of the grid-connection
point for triggering inverter
shutdown.
The default value is 20. This
parameter specifies the duration
threshold of high feed-in power for
triggering inverter shutdown.
● When High feed-in power
duration threshold for triggering
inverter shutdown is set to 5,
Shutdown at high feed-in power
takes precedence.
● When High feed-in power
duration threshold for triggering
inverter shutdown is set to 20,
Grid connection with limited
power takes precedence (when
Active power control is set to
Grid connection with limited
power).
78