Advertisement

Programming
NFS2-640, NFS-320/SYS
MN network mapping allows the programmer to
select the Noti•Fire•Net nodes from which the
NFS2-640 or NFS-320/SYS will accept an MN
alarm message to initiate fire suppression.
On the NFS2-640 or NFS-320/SYS Network Map-
ping branch of VeriFire Tools, check the appropriate
boxes in the Mass Notification mapping column.
DVC
DVC MN mapping consists of:
Creating a logic equation for the MN Active Tone that will activate if a ZF20 MN alarm comes in from any MN-mapped node.
Refer to Section 3.3.7 on page 25 for this programming.
All Call mapping in VeriFire Tools. MN pages will go out to the nodes in this map. Refer to the programming section of the DVC
manual for VeriFire Tools programming.
3.3.5 Type IDs
Program inputs and outputs dedicated to mass notification with MN Type IDs. Outputs with combined functions may use other type IDs.
Table 3.1 lists and describes MN monitor module Type IDs.
Type Code
ECS/MN MONITOR
ECS/MN SUPT
ECS/MN SUPL
ECS/MN TROUBLE
MON
Monitor module activations with these Type IDs will generate mass notification events locally and over a network. Trouble conditions at
these points will generate an MN trouble.
24
Figure 3.13 MN Mapping, NFS2-640/NFS-320/SYS
Latching
Point Type
Activates
(Y=yes
N=no)
MN Alarm
Y
MN
N
Supervisory
MN
Y
Supervisory
Trouble
N
Table 3.1 MN Monitor Type IDs
Point Characteristics
Device Function
CBE
Y
Mass Notification alarm monitoring device.
Y
Indicates tracking supervisory condition.
Y
Indicates latching supervisory condition.
N
Generates a trouble for both short and open
circuit conditions.
Mass Notification — P/N LS10063-000NF-E:E 06/26/2019
Programming