• When offline auto tuning ends, press
the start signal (STF signal or STR signal). This operation resets the offline auto tuning, and the PU's monitor display
returns to the normal indication. (Without this operation, next operation cannot be started.)
NOTE
• The motor constants measured once in the offline auto tuning are stored as parameters and their data are held until the
offline auto tuning is performed again. However, the tuning data is cleared by performing all parameter clear.
• Changing Pr.71 (Pr.450) after tuning completion will change the motor constant. For example, if Pr.71 = "3" is set after
tuning is performed with Pr.71 = "0", the tuning data becomes invalid. Set Pr.71 = "0" again for using the tuning data.
• If offline auto tuning has ended in error (see the table below), motor constants are not set. Perform an inverter reset and
restart tuning.
Error display
8
9
91
92
93
94
• When tuning is ended forcibly by pressing
tuning does not end properly. (The motor constants have not been set.) Perform an inverter reset and restart tuning.
NOTE
• An instantaneous power failure occurring during tuning will result in a tuning error. After power is restored, the inverter
starts normal operation. Therefore, when STF (STR) signal is ON, the motor runs in the forward (reverse) rotation.
• Any alarm occurring during tuning is handled as in the normal operation. Note that even if a retry operation has been set,
retry is not performed.
• The set frequency monitor displayed during the offline auto tuning is 0 Hz
CAUTION
• Note that the motor may start running suddenly.
• For the offline auto tuning in vertical lift applications, etc., caution is required to avoid falling due to insufficient torque.
358
5. PARAMETERS
5.10 (C) Motor constant parameters
on the operation panel during PU operation. For External operation, turn OFF
Error cause
Forced end
Inverter protective function operation
The current limit (stall prevention) function is
activated.
The converter output voltage has dropped to
75% of the rated voltage.
Calculation error
The motor is not connected.
Rotation tuning frequency setting error
(The frequency command for the tuning was
given to exceed the maximum frequency setting,
or to be in the frequency jump range.)
Set Pr.96 (Pr.463) = "1" or "101" and try again.
Make the setting again.
Set the acceleration/deceleration time longer.
Set Pr.156 = "1".
Check for the power supply voltage fluctuation.
Check the Pr.83 Rated motor voltage (Pr.456
Rated second motor voltage) setting.
Check the Pr.83 and Pr.84 settings.
Check the motor wiring and make the setting again.
Check the Pr.1 Maximum frequency and Pr.31 to
Pr.36 Frequency jump settings.
or turning OFF the start signal (STF or STR) during tuning, offline auto
Countermeasures