Huawei LUNA2000-100KTL-M1 User Manual page 99

Smart power control system
Hide thumbs Also See for LUNA2000-100KTL-M1:
Table of Contents

Advertisement

LUNA2000-100KTL-M1 Smart Power Control System
User Manual
Alarm
Alarm
ID
Name
2087
Internal
Fan
Abnormal
2095
Manageme
nt System
Certificate
Invalid
2096
Manageme
nt system
certificate
to expire
2097
Manageme
nt system
certificate
expired
2098
Parallel
System
Communica
tion Failure
Issue 02 (2023-01-10)
Severi
Possible Cause
ty
Major
Cause ID = 1–4
The internal fan is short-
circuited, the power supply is
insufficient, or the fan is
damaged.
Warni
Cause ID = 1
ng
The digital signature
certificate is invalid.
Warni
Cause ID = 1
ng
The digital signature
certificate is about to expire.
Major
Cause ID = 1
The digital signature
certificate has expired.
Major
Cause ID = 1
The parallel communication
line is abnormal.
Copyright © Huawei Technologies Co., Ltd.
8 Alarm Reference
Suggestion
Turn off the AC switch and DC
switch, wait for 5 minutes, and
then turn on the AC switch and
DC switch. If the fault persists
after the device runs for 5
minutes, contact your dealer or
technical support to replace
the device.
Check the time or replace the
digital signature certificate.
Replace the digital signature
certificate in time.
Replace the digital signature
certificate immediately.
Power off the devices
connected to the same DC bus
(turn off the AC switches and
DC switches, and wait for a
period specified on the device
safety warning label), and then
perform the following
operations:
Check that the
communications cable is
securely connected and turn on
the AC switches and DC
switches. If the fault persists,
contact your dealer or
technical support.
93

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents