Representation of analog values
C.2 Representation of analog values in voltage measuring ranges
C.2
Representation of analog values in voltage measuring ranges
The following tables list the decimal and hexadecimal values (codes) of the possible voltage
measuring ranges.
Table C- 4
Values
dec
32767
32511
27649
27648
20736
1
0
-1
-20736
-27648
-27649
-32512
-32768
Table C- 5
Values
dec
32767
32511
27649
27648
20736
1
0
-1
-4864
-32768
46
Voltage measuring range ±10 V and ±5 V
Voltage measuring range
hex
±10 V
7FFF
>11.759 V
7EFF
11.759 V
6C01
6C00
10 V
5100
7.5 V
1
361.7 µV
0
0 V
FFFF
AF00
-7.5 V
9400
-10 V
93FF
8100
-11.759 V
8000
< -11.759 V
Voltage measuring range 1 to 5 V
Voltage measuring range
hex
1 to 5 V
7FFF
>5.704 V
7EFF
5.704 V
6C01
6C00
5 V
5100
4 V
1
1 V + 144.7 µV
0
1 V
FFFF
ED00
0.296 V
8000
< 0.296 V
±5 V
>5.879 V
5.879 V
5 V
3.75 V
180.8 µV
0 V
-3.75 V
-5 V
-5.879 V
< -5.879 V
Analog Input Module AI 8xU/I HS (6ES7531-7NF10-0AB0)
Range
Overflow
Overshoot range
Rated range
Undershoot range
Underflow
Range
Overflow
Overshoot range
Rated range
Undershoot range
Underflow
Manual, 07/2014, A5E03484886-AC