Representation Of Analog Values In Voltage Measuring Ranges - Siemens SIMATIC S7-1500 Manual

Analog input module ai 8xu/i hs
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Representation of analog values
C.2 Representation of analog values in voltage measuring ranges
C.2

Representation of analog values in voltage measuring ranges

The following tables list the decimal and hexadecimal values (codes) of the possible voltage
measuring ranges.
Table C- 4
Values
dec
32767
32511
27649
27648
20736
1
0
-1
-20736
-27648
-27649
-32512
-32768
Table C- 5
Values
dec
32767
32511
27649
27648
20736
1
0
-1
-4864
-32768
46
Voltage measuring range ±10 V and ±5 V
Voltage measuring range
hex
±10 V
7FFF
>11.759 V
7EFF
11.759 V
6C01
6C00
10 V
5100
7.5 V
1
361.7 µV
0
0 V
FFFF
AF00
-7.5 V
9400
-10 V
93FF
8100
-11.759 V
8000
< -11.759 V
Voltage measuring range 1 to 5 V
Voltage measuring range
hex
1 to 5 V
7FFF
>5.704 V
7EFF
5.704 V
6C01
6C00
5 V
5100
4 V
1
1 V + 144.7 µV
0
1 V
FFFF
ED00
0.296 V
8000
< 0.296 V
±5 V
>5.879 V
5.879 V
5 V
3.75 V
180.8 µV
0 V
-3.75 V
-5 V
-5.879 V
< -5.879 V
Analog Input Module AI 8xU/I HS (6ES7531-7NF10-0AB0)
Range
Overflow
Overshoot range
Rated range
Undershoot range
Underflow
Range
Overflow
Overshoot range
Rated range
Undershoot range
Underflow
Manual, 07/2014, A5E03484886-AC

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic et 200mp6es7531-7nf10-0ab0

Table of Contents