Huawei SUN2000-4.95KTL-JPL0 User Manual page 64

Hide thumbs Also See for SUN2000-4.95KTL-JPL0:
Table of Contents

Advertisement

SUN2000-4.95KTL-JPL0
User Manual
Alarm ID
Alarm
Name
2063
Cabinet
Overtem
perature
2064
Device
Fault
2065
Upgrade
Failed or
Version
Mismatch
61440
Faulty
Monitori
ng Unit
2070
Active
Islanding
Issue 04 (2023-02-17)
Alarm
Cause
Severity
Minor
Cause ID = 1
● The solar inverter is
installed in a place with
poor ventilation.
● The ambient
temperature is too high.
● The solar inverter is not
working properly.
Major
Cause ID = 1–12
An unrecoverable fault has
occurred on a circuit inside
the solar inverter.
Minor
Cause ID = 1, 2 and 4
The upgrade does not
complete normally.
Minor
Cause ID = 1
● The flash memory is
insufficient.
● The flash memory has
bad sectors.
Major
Cause ID = 1
When the power grid
experiences an AC power
outage, the solar inverter
detects islanding
proactively.
Copyright © Huawei Technologies Co., Ltd.
7 System Maintenance
Suggestions
1. Check the ventilation and
ambient temperature of the
solar inverter installation
position.
2. If the ventilation is poor or
the ambient temperature
exceeds the upper threshold,
improve the ventilation and
heat dissipation.
3. If the ventilation and
ambient temperature both
meet requirements, contact
your dealer or Huawei
technical support.
Turn off the AC output switch
and DC input switch, and then
turn them on after 5 minutes. If
the fault persists, contact your
dealer or Huawei technical
support.
1. Perform an upgrade again.
2. If the upgrade fails for
multiple times, contact your
dealer or Huawei technical
support.
Turn off the AC output switch
and then the DC input switch.
After 5 minutes, turn on the AC
output switch and then the DC
input switch. If the fault persists,
replace the monitoring board or
contact your dealer or Huawei
technical support.
Check that the grid connection
voltage of the solar inverter is
normal.
58