TP48200A-HX09A3, TP48200A-HX09A4,
TBC300A-DCA3, TBC300A-DCA5 and
TBC300A-TCA2 Telecom Power
User Manual
Measures
1.
2.
4.2.19 Rect Fault
Possible Causes
Measures
1.
2.
4.2.20 Rect Protection
Possible Causes
Measures
1.
2.
3.
4.
4.2.21 Rect Comm Fault
Possible Causes
Issue 04 (2019-11-15)
The smoke sensor is faulty.
Check whether there is smoke inside the cabinet. If so, disconnect the power supply from
the cabinet, handle the fault, and then restart the system and clear the alarm on the SMU.
Check whether the smoke sensor is faulty. If the smoke sensor is faulty, replace it.
Rectifier connections are loose.
A rectifier is faulty.
Check the Fault indicator on the rectifier panel. If it is steady red, remove the rectifier,
and then reinstall it after the indicator turns off.
If the alarm persists, replace the rectifier.
The rectifier input voltage is too high.
The rectifier input voltage is too low.
The ambient temperature is too high.
The rectifier is abnormal.
Check whether the AC input voltage exceeds the upper threshold for rectifier working
voltage. If so, locate and rectify the power supply fault and restore the power supply.
Check whether the AC input voltage is below the lower threshold for rectifier working
voltage. If so, locate and rectify the power supply fault and restore the power supply.
Check whether the ambient temperature is higher than the maximum operating
temperature of the rectifier. If so, locate and rectify the temperature control system fault.
Remove the rectifier that has generated the alarm and reinstall it after the indicator turns
off. If the alarm persists, replace the rectifier.
A rectifier has been removed.
Rectifier connections are loose.
A rectifier is faulty.