Haier 5U125S2PN1FA Installation Manual

Haier 5U125S2PN1FA Installation Manual

Multi-split air conditioner

Advertisement

MULTI-SPLIT AIR CONDITIONER
INSTALLATION MANUAL
Original Instructions
0150558811
This product must only be installed or serviced by qualified personnel.
Please read this manual carefully before installation.This appliance is filled with R32.
Keep this manual for future reference.
Original instructions
3U55S2PR1FA
4U71S2PR1FA
4U80S2PR1FA
5U100S2PS1FA
5U125S2PN1FA
5U125S2PN1FA
Contents
Safety Precautions
Move and scrap the air conditioning
Accessories
outdoor units
Precautions on Installation
19
23
30

Advertisement

Table of Contents
loading

Summary of Contents for Haier 5U125S2PN1FA

  • Page 1: Table Of Contents

    Wiring work 5U100S2PS1FA Dred function Test running Trouble shooting 5U125S2PN1FA 5U125S2PN1FA 0150558811 This product must only be installed or serviced by qualified personnel. Please read this manual carefully before installation.This appliance is filled with R32. Keep this manual for future reference.
  • Page 2 parliament,herewith we inform the consumer about the dis- posal requirements of the electrical and electronic products. DISPOSAL REQUIREMENTS: IMPORTANT INFORMATION REGA- Your air conditioning product is marked with this RDING THE REFRIGERANT USED symbol.This means that electrical and electronic products shall not be mixed with unsorted household waste.Do not try to dismantle the Contains fluorinated greenhouse gases system yourself:the dismantling of the air...
  • Page 3 The air conditioner can not be discarded or scrapped Randomly If you need please contact customer service personnel of Haier to scrap in order to obtain the correct disposal methods. Reusable mechanical connectors and flared joints are not allowed indoor.
  • Page 4 Safety Precautions WARNING The installation, maintenance, service and repair operations of this product shall be carried out by professional personnel, who have been trainedand certified by national training organizations that areaccredited to teach the relevant national competency standards that may be set in legislation. Improper installation may cause water leakage, electrical shock, fire, or explosion.
  • Page 5 CAUTION Do not install the air conditioner in a place where there is danger of exposure to inflammable gas leakage. If the gas leaks and builds up around the unit, it may catch fire or explosion. Establish drain piping according to the instructions of this manual. Inadequate piping may cause flooding.
  • Page 6 Minimum Room Area Total Mass Charged/kg Type kg/m3 Minimum Room Area/m 1.224 1.836 2.448 3.672 4.896 6.12 7.956 0.306 Safety Awarenes 1.Procedures: operation shall be made as per controlled procedures to minimize the probability of risks. 2.Area: area shall be divided and isolated appropriately, and operation in an enclosed space shall be avoided. Before the refrigeration system is started or before working, ventilation or opening of the area shall be guaranteed.
  • Page 7 Electrical Safety Requirements 1.The surrounding conditions (ambient temperature, direct sunlight and rainwater) shall be noticed during electrical wiring, with effective protective measures being taken. 2.Copper wire cable in line with local standards shall be used as the power line and connector wire. 3.Both the indoor unit and outdoor unit shall be reliably earthed.
  • Page 8 1) Fixing The support of the outdoor unit shall be fixed onto the wall surface, and then the outdoor unit shall be fixed onto the support horizontally. In case the outdoor unit is wall-mounted or roof-mounted, the support shall be firmly fixed, to avoid the damage of strong wind.
  • Page 9 Relocation Procedures Please call the dealer or the appointed agency. Follow the following procedures: Inspection on system leakage prior Disassembly Safety discharge of refrigerant to disassembly Inspection on operational state Disassembly Safety discharge of refrigerant Refrigerant recovery by the system Cleaning of the indoor unit and connecting pipes with inert gas Disassembly...
  • Page 10 Inspection on Maintenance Environment Before operation, the refrigerant leaked in the room is not allowed. The area of the room in which maintenance is made shall be in line with this manual. Continuous ventilation shall be maintained during maintenance. Open fire or high-temperature heat source higher than 548 degree which can easily give birth to open fire is not allowed inside the room within the maintenance area.
  • Page 11 Maintenance Items Maintenance Requirements Before the refrigeration system is operated, the circulating system shall be cleaned with nitrogen. Afterwards, the outdoor unit shall be vacuumized, the duration of which cannot be less than 30 minutes. Finally, 1.5~2.0MPa OFN shall be used for nitrogen flushing (30 seconds~1 minute), to confirm the position requiring treatment.
  • Page 12 Refrigerant Charging Procedures The following requirements are added as the supplementation of conventional procedures: During the use of refrigerant charging tools, cross contamination of different refrigerants shall be avoided. The total length (including the refrigerant pipelines) shall be shortened as much as possible, to reduce the residual of refrigerant inside; The cylinders of refrigerant shall be kept upright;...
  • Page 13 Carefully read the following information in order to operate the air conditioner correctly. Below are listed three kinds of Safety Precautions and Suggestions. Incorrect operations may result in severe consequences of death or serious injuries. WARNING Incorrect operations may result in injuries or machine damages; in some cases may cause serious consequences. CAUTION INSTRUCTIONS: These information can ensure the correct operation of the machine.
  • Page 14 WARNING Have the unit professionally installed. Be sure to carefully follow each step in this handbook when Improper installation by an unqualified person may result installing the unit. in water leak, electric shock, fire, or explosion. Improper installation may result in water leak, electric shock, smoke or fire.
  • Page 15 Precautions for Handling Units for Use with R32 Caution Do not use the existing refrigerant piping Use a vacuum pump with a reverse-flow check valve. The old refrigerant and refrigerator oil in the existing piping If other types of valves are used, the vacuum pump oil will contain a large amount of chlorine, which will cause the flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate.
  • Page 16 Before Installing (Relocating) the Unit or Performing Electric Work Caution Ground the unit. Do not spray water on the air conditioners or immerse the Do not connect the grounding on the unit to gas pipes,water air conditioners in water. pipes, lightning rods, or the grounding terminals of Water on the unit presents a risk of electric shock.
  • Page 17: Read Before Installation

    Read Before Installation Items to Be Checked (1) Verify the type of refrigerant used by the unit to be serviced. Refrigerant Type: R32 (2) Check the symptom exhibited by the unit to be serviced. Look in this service handbook for symptoms relating to the refrigerant cycle.
  • Page 18 R32 leakage Test No changes from the conventional method. Note that a refrigerant leakage detector for R22 or R410A cannot detect R32 leakage. Halide torch R22 or R407C leakage detector Items to be strictly observed : Pressurize the equipment with nitrogen up to the design pressure and then judge the equipment's air tightness, taking temperature variations into account.
  • Page 19: Procedure For Selecting The Location

    Accessories Accessories supplied with the outdoor unit: 5U125S2PN1FA Drawing Name of parts Quantity Drainage elbow Rubber cushion Clap Procedure for Selecting the Location 1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified.
  • Page 20 Procedure for Selecting the Location 6) For seacoast applications, block the unit from direct exposure to sea breeze by installing the unit behind a structure (such as a building) or a protective wall that is 1.5 times higher than the unit, leaving 700 mm of space between the wall and unit for air circulation.Consult an installation expert about taking anti-corrosion measures, such as removing salinity on the heat exchanger and applying a rust inhibitor more frequently than once a year.
  • Page 21: Installation Drawings Of Indoor And

    Installation drawings of indoor and outdoor units Do not connected the embedded branch piping and the outdoor unit when only carrying out piping work without connecting the indoor unit in order to add another indoor unit later. Make sure no dirt or moisture gets into either side of the embedded branch piping. Installation figure please refers to the following.
  • Page 22: Outdoor Unit Installation

    (The shorter the refrigerant piping, the better the performance. Connect so that the piping is as short as possible. Shortest allowable length per room is 3m) 4U71S2PR1FA 3U55S2PR1FA 5U100S2PS1FA 5U125S2PN1FA Outdoor unit capacity class 4U80S2PR1FA 25m max. 25m max.
  • Page 23: Refrigerant Piping Work

    Limitations on the installation Indoor Unit Level Outdoor Unit difference: 15m max. Level difference: Outdoor Unit Level Level 15m max. difference: difference: 7.5m max. 7.5m max. Indoor Unit If the outdoor unit is positioned higher than one or more indoor units. If the outdoor unit is positioned higher than all indoor units.
  • Page 24 Refrigerant piping work 3. Refrigerant piping work 1). Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches. Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas. Flare nut tightening torque Flare nut for 6.35...
  • Page 25 4U71S2PR1FA 4U80S2PR1FA 5U100S2PS1FA 100m 5U125S2PN1FA 7.Precautions for Laying Refrigerant Piping Cautions on pipe handling 1) Protect the open end of the pipe against dust and moisture. 2) All pipe bends should be as gentle as possible. Use a pipe bender for bending.(Bending radius should be 30 to 40mm or larger.)
  • Page 26 3) Use separate thermal insulation pipes for gas and liquid refrigerant pipe. Wall Inter unit wiring Be sure to Gas pipe place a cap. Liquid pipe Rain If no flare cap is available, cover the flare mouth with tape Liquid pipe Gas pipe to keep dirt or water insulation...
  • Page 27: Pump Down Operation

    Pump Down Operation In order to protect the environment, be sure to pump down when relocating or disposing of the unit. 1) Remove the valve caps from liquid stop valve and gas stop valve. 2) Carry out forced cooling operation. liquid 3) After five to ten minutes, close the liquid stop valve with a hexagonal wrench.
  • Page 28 Wiring work Valve cover Terminal block 4. Wiring method of indoor unit Loosen wire cover and connect the power cord and communication wire of indoor unit to the terminal correspondingly. Note: When connecting power cord to power supply terminal, please pay attention to the following items: Do not connect the power cord with different dimensions to the same connection wire end.
  • Page 29: Dred Function

    Dred function Please consult your reseller and/or installer to determine if you have a DRED device. Connect output from your DRED device (where available) to the RJ45connector on the outdoor unit, as shown. 1. Open cover piece and locate the fixed DRM cable. a.
  • Page 30: Test Running

    3U55S2PR1FA and are with 3 green LED that means 3 indoor units,4U71S2PR1FA and 4U80S2PR1FA with 4 green LED means 4 indoor units. 5U100S2PS1FA and 5U125S2PN1FA with 5 green LED means 5 indoor units. If one LED keep lighting that means the corresponding indoor unit has good communication with outdoor unit. If one LED is not lighting, that means there is no communication between indoor and outdoor.unit has good commmunication with outdoor unit.
  • Page 31: Trouble Shooting

    Trouble shooting Possible reasons Outdoor LED Wired Cassette and convertible display controller indoor display outdoor error display code use the timer and runing lamp Timer lamp Running lamp flash time flash time Faulty of outdoor unit EEPROM IPM overcurrent or short circuit Communication failure between Module and ECU Module operated overload Module low or high voltage...
  • Page 32 Address:Haier Industrial Park,Qianwangang Road,Eco-Tech Development Zone,Qingdao 266555,Shandong,P.R.C. Contacts: TEL +86-532-88936943; FAX +86-532-8893-6999 Website: www.haier.com...