EN

6.4. Modbus setup

The METPOINT
FLM thermal flow meter is equipped with a RS 485 interface (Modbus RTU). Before starting the sensor, configure
®
the communication parameters
ModBus ID, baud rate, parity and stop bit
to enable communication with the Modbus master.
Setup → ModBus Setup
Default (factory) settings:
Modbus ID:
1
Baud rate:
19200
Stop bit:
1
Parity:
even
Caution:
If the sensor is the last device in the Modbus system, it must be terminated. For further information, see sec. "4.5. Modbus final
termination" on page 26.
METPOINT
SF53
®
Save the settings by pressing the "Save" button.
To apply the default (factory) settings, press the "Set to De-
fault" button.
Installation and operating manual