Setting Procedures; Step1: Use Settings [Ch Use_Ch*] - Toshiba GRB200 Instruction Manual

Replica setting procedure for centralized busbar protection ied
Hide thumbs Also See for GRB200:
Table of Contents

Advertisement

Setting procedures

3
It has been discussed about the settings with regard to bay arrangements in the preceding
chapter, but the user may concern the setting procedures for actual busbar structures.
An example of busbar structure is shown with a single line diagram in Figure 3-1. The figure
illustrates that feeders and couplers are structured with CHs. All CHs can have forward
looking protection-zones, but 'CH4' can have a revers looking one exclusively. We discuss about
the setting examples step by step in this chapter; the user can read the settings by referencing
the models described in
Busbar-W1
Busbar-W2
DS-
WF1
CB-
WF
West Feeder
Bay gear types:
DS
CB
CT

Step1: Use settings [CH use_CH*]

It is required to set On for settings [CH use_CH1] to [CH_use_CH7] in the example. The [CH
use_CH8], etc. can be left with default Off settings.
Appendixes
DS-
DS-
DS-
WC1
WC2
WF2
CB-
WC
West Coupler
CH types:
CH looking in forward:
(Symbol[→] shows right is forward)
CH looking in both sides:
(In the above, right side[→] is forward and left side[←] is reverse)
Figure 3-1 Example: single line diagram
.
North Section
DS-NS1
CB-NS
CH4
South Section
DS-SS1
CB-SS
CH6
CH5
- 19 -
6F2S1923 (0.03)
DS-NS2
Busbar-E1
DS-SS2
Busbar-E2
DS-
DS-
EF1
EF2
CB-
EF
East Feeder
GRB200C (Replica)