Condensate Piping - Haier GE APPLIANCES NF96US Installation Instructions Manual

Warm air gas furnace upflow/ horizontal left/right air discharge direct vent & non-direct vent
Hide thumbs Also See for GE APPLIANCES NF96US:
Table of Contents

Advertisement

Condensate Piping

This unit is designed for either right or left side exit of
condensate piping in upflow applications. In horizontal
applications, the condensate trap must extend below the
unit. An 8" service clearance is required for the condensate
trap. Refer to Figure 49 for condensate trap locations.
Figure 56 shows trap assembly using 1/2" PVC or 3/4"
PVC.
CONDENSATE TRAP AND PLUG LOCATIONS
(Unit shown in upflow position)
Trap
(same on
right side)
1-1/2 in.
NOTE - In upflow applications where side return air
filter is installed on same side as the condensate
trap, filter rack must be installed beyond condensate
trap or trap must be relocated to avoid interference.
Figure 49.
NOTE: If necessary the condensate trap may be installed
up to 5' away from the furnace. Use PVC pipe to connect
trap to furnace condensate outlet. Piping from furnace
must slope down a minimum of 1/4" per ft. toward trap.
1.
Determine which side condensate piping will exit the
unit, location of trap, field-provided fittings and length
of PVC pipe required to reach available drain.
2.
Use a large flat head screw driver or a 1/2" drive
socket extension and remove plug (Figure 49) from
the cold end header box at the appropriate location
on the side of the unit. Install provided 3/4 NPT street
elbow fitting into cold end header box. Use Teflon tape
or appropriate pipe dope.
3.
Install the cap over the clean out opening at the base
of the trap. Secure with clamp. See Figure 51.
4.
Install drain trap using appropriate PVC fittings, glue
all joints. Glue the provided drain trap as shown in
Figure 56. Route the condensate line to an open drain.
Condensate line must maintain a 1/4" downward slope
from the furnace to the drain.
507768-05G / 31-5000655
5.
Plug
(same on
left side)
Do not use copper tubing or existing copper condensate
lines for drain line.
6.
Condensate line must slope downward away from the
trap to drain. If drain level is above condensate trap,
condensate pump must be used. Condensate drain line
should be routed within the conditioned space to avoid
freezing of condensate and blockage of drain line.
A separate drain line must be run to the drain from the
condensate trap to ensure proper drainage and pressure
switch operation. DO NOT connect the condensate trap
drain into the drain line from the evaporator coil.
Issue 2223
Figure 52 and Figure 53 show the furnace and
evaporator coil using a separate drain. If necessary
the condensate line from the furnace and evaporator
coil can drain together. See Figure 54 and Figure 55.
Upflow furnace (Figure 50) - In upflow furnace
applications the field provided vent must be a minimum
1" to a maximum 2" length above the condensate drain
outlet connection. Any length above 2" may result in a
flooded heat exchanger if the combined primary drain
line were to become restricted.
Horizontal furnace (Figure 52) - In horizontal furnace
applications the field provided vent must be minimum
4" to a maximum 5" length above the condensate drain
outlet connection. Any length above 5" may result in a
flooded heat exchanger if the combined primary drain
line were to become restricted.
NOTE: In horizontal applications it is recommended to
install a secondary drain pan underneath the unit and
trap assembly.
NOTE: Vinyl tubing may be used for condensate drain.
Tubing must be 1-1/4" o.d. X 1" i.d. and should be
attached to the drain on the trap using a hose clamp.
CAUTION
If unit will be started immediately upon completion of
installation, prime trap per procedure outlined in Unit
Start-Up section.
CAUTION
Page 33 of 56

Advertisement

Table of Contents
loading

Table of Contents