Mitsubishi Electric MELSEC iQ-R Series User Manual page 165

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

When the D LINK LED turns off or is flashing
When the D LINK LED turns off or is flashing, check the following.
Check item
Is the master station operating normally?
Is the master station connected to the network?
Does the IP address of each station match the
"Network Configuration Settings" under "Basic
Settings" of the master station?
In the "Network Configuration Settings" under
"Basic Settings", are the third and fourth octets of
the IP address of the master station overlapped
with those of any other stations?
In the "Network Configuration Settings" under
"Basic Settings", does the network address
(subnet mask part) of the IP address of the master
station match that of other stations?
Are the third and fourth octets of the IP address
set to all 0 or all 1?
Is the host address of the IP address set to all 0 or
all 1?
Is a reserved address set to the IP address?
Do the used Ethernet cables conform to the
Ethernet standard?
Is the switching hub used operating normally?
Does the station-to-station distance meet the
specifications?
Does the cabling condition (bending radius) meet
the specifications?
Is any Ethernet cable disconnected?
Is the connection different from the one set for
"Network Topology" under "Basic Settings" of the
master station?
Has the time synchronization source station been
reset?
Is the time synchronization source station turned
off?
Is the time synchronization source station
operating normally?
Has any other station been reset?
Are other stations turned off?
Are other stations connected to the RJ71GN11-T2
operating normally?
Is there any other station that has not set an IP
address?
Is there any other station that is not set in
"Network Configuration Settings" under "Basic
Settings" of the master station?
Is a network topology with restrictions used for
connection?
Are station numbers unique?
Is the IP address overlapped with another station?
Are 121 or more slave stations connected?
Are Ethernet devices properly connected to a
network line?
Action
• If an error has occurred in the CPU module on the master station, eliminate the cause of the CPU
module error. ( MELSEC iQ-R CPU Module User's Manual (Application))
• If an error occurs in the RJ71GN11-T2 in the master station, take action according to the module
diagnosis procedure. ( Page 166 Checking the Module Status)
Connect the master station to the network.
Correct the setting of the IP address in "Network Configuration Settings" under "Basic Settings" of the
master station.
• Set IP addresses in a way that does not overlap the third to fourth octets of the IP address in all stations.
• Set the IP address and subnet mask to match the network addresses of all stations.
• Set the third and fourth octets of the IP address to values other than all 0 or all 1.
• Set the host address of the IP address to values other than all 0 or all 1.
• Set an IP address other than a reserved address.
Replace the cables with Ethernet cables which conform to the standard. ( MELSEC iQ-R CC-Link IE
TSN User's Manual (Startup))
• Use a switching hub that conforms to the standard. ( MELSEC iQ-R CC-Link IE TSN User's Manual
(Startup))
• Power off and on the switching hub.
Set the station-to-station distance within range. ( MELSEC iQ-R CC-Link IE TSN User's Manual
(Startup))
Refer to the manual for the Ethernet cable, and correct the bending radius.
Replace the Ethernet cable.
Correct the wiring according to "Network Topology" under "Basic Settings" of the master station. (
Page 102 Network Topology)
• Since a station is temporarily disconnected after switching the time synchronization source, wait for it to
return.
• Avoid unnecessary disconnections or returns in a station that is the time synchronization source.
Check the manual of the module used for the time synchronization source station.
• Avoid unnecessary reset, since a station is disconnected while resetting.
• Start other stations.
Power on other stations.
• Check if the modules on the other stations are performing data link using CC-Link IE TSN/CC-Link IE
Field diagnostics. ( Page 169 Checking the Network Status)
• Check the operation status of modules on other stations. ( User's manual for the module used)
Set the IP address for the slave station for which the IP address is not set.
Set the connected slave station to "Network Configuration Settings" under "Basic Settings" of the master
station.
Correct the wiring. ( MELSEC iQ-R CC-Link IE TSN User's Manual (Startup))
Change the overlapped station number.
Change the IP address of the overlapped station.
Change the connection of the slave stations to 120 stations or less.
Correct the mixed structure of the Ethernet device. ( MELSEC iQ-R CC-Link IE TSN User's Manual
(Startup))
4 TROUBLESHOOTING
163
4.1 Checking with LED
4

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r cc-link ie tsn

Table of Contents