LIFE OF INVERTER PARTS
(1) Life warning display and signal output (Y90 signal, Pr.255)
• Whether the parts of the control circuit capacitor, main circuit capacitor, cooling fan, and
inrush current limit circuit have reached the life warning output level or not, can be checked
with E700 (Pr.255) and the life alarm signal (Y90).
bit
15
7
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
E700 (Pr.255)
(decimal)
• The life alarm signal (Y90) turns ON when any of the control circuit capacitor, main circuit
capacitor, cooling fan, or inrush current limit circuit reaches the life warning output level.
• For the terminal used for the Y90 signal, set "90" (positive logic) or "190" (negative logic) in
any of M400 to M406 (Pr.190 to Pr.196) (output terminal function selection).
Remark
Changing the terminal assignment by using M400 to M406 (Pr.190 to Pr.196) (output
terminal function selection) may affect the other functions. Set parameters after confirming
the function of each terminal.
8.2 Inverter parts life display
138
0
1
bit 0 Control circuit capacitor life
bit 1 Main circuit capacitor life
bit 2 Cooling fan life
bit 3 Inrush current limit circuit life
bit
Inrush current
(binary)
limit circuit life
15
1111
14
1110
13
1101
12
1100
11
1011
10
1010
9
1001
8
1000
7
0111
6
0110
5
0101
4
0100
3
0011
2
0010
1
0001
0
0000
When using an option (FR-A8AY, FR-A8AR, FR-A8NC), the life can be output
separately to the Control circuit capacitor life (Y86) signal, Main circuit capacitor
life (Y87) signal, Cooling fan life (Y88) signal, and Inrush current limit circuit life
(Y89) signal.
●E700 (Pr.255) read
Cooling fan
life
●E700 (Pr.255)
setting read
Bit image is
displayed in decimal.
Main circuit
Control circuit
capacitor life
capacitor life
: With warnings, : Without warnings