34

9.3.2. Adapter Information Special Register (0x1100, 4352)

Address
Access
0x1102(4354)
Read
0x1103(4355)
Read
0x1104(4356)
Read
0x1105(4357)
Read
0x1106(4358)
Read
0x1107(4359)
Read
0x1108(4360)
Read
0x1109(4361)
Read
0x110D(4365)
Read
0x110E(4366)
Read
0x1110(4368)
Read
0x1113(4371)
Read
0x1119(4377)
Read
0x111D(4381)
Read
* ** After the system is reset, the new "Set Value" action is applied.
** If the slot location is changed, set default value automatically (all expansion slot is live).

9.3.3. Expansion Slot Information Special Resister (0x2000, 8192)

Each expansion slot has 0x20(32) address offset and same information structure.
Slot#1 0x2000(8192)~0x201F(8223)
Slot#3 0x2040(8256)~0x205F(8287)
Slot#5 0x2080(8320)~0x209F(8351)
Slot#7 0x20C0(8384)~0x20DF(8415)
Slot#9 0x2100(8448)~0x211F(8479)
Slot#11 0x2140(8512)~0x215F(8543)
Slot#13 0x2180(8576)~0x219F(8607)
Slot#15 0x21C0(8640)~0x21DF(8671) Slot#16 0x21E0(8672)~0x21FF(8703)
Slot#17 0x2200(8704)~0x221F(8735)
Slot#19 0x2240(8768)~0x225F(8799)
Slot#21 0x2280(8832)~0x229F(8863)
Slot#23 0x22C0(8896)~0x22DF(8927) Slot#24 0x22E0(8928)~0x22FF(8959)
Slot#25 0x2300(8960)~0x231F(8991)
Slot#27 0x2340(9024)~0x235F(9055)
Slot#29 0x2380(9088)~0x239F(9119)
Slot#31 0x23C0(9152)~0x23DF(9183) Slot#32 0x23E0(9184)~0x23FF(9215)
Slot#33 0x2400(9216)~0x241F(9247)
.....
Slot#63 0x27C0(10176)~0x27DF(10207)
Type, Size
Description
1word
Start address of input image word register. =0x0000
1word
Start address of output image word register. =0x0800
1word
Size of input image word register.
1word
Size of output image word register.
1word
Start address of input image bit. = 0x0000
1word
Start address of output image bit. =0x1000
1word
Size of input image bit.
1word
Size of output image bit.
1word
Field Power & Node ID Dip Switch State.
ex) Field Power ON, Dip SW On = 10000000 11111111
Up to 33word
Expansion slot's RIO3-number including GN
First 1word is adapter's number, if GN-9289, then 0x9289
1word
Number of expansion slot
Up to 33word
Expansion slot Module Id. Refer to Appendix A.1 Product List.
First 1word is adapter's module id.
1word
Hi byte is ModBus status, low byte is internal status.
Zero value means 'no error'.
1word
Adapter HX-RIO3 Series Revision. If 0x013C, HX-RIO3 Series
Revision is 1.60
Slot#2 0x2020(8224)~0x203F(8255)
Slot#4 0x2060(8288)~0x207F(8319)
Slot#6 0x20A0(8352)~0x20BF(8383)
Slot#8 0x20E0(8416)~0x20FF(8447)
Slot#10 0x2120(8480)~0x213F(8511)
Slot#12 0x2160(8544)~0x217F(8575)
Slot#14 0x21A0(8608)~0x21BF(8639)
Slot#18 0x2220(8736)~0x223F(8767)
Slot#20 0x2260(8800)~0x227F(8831)
Slot#22 0x22A0(8864)~0x22BF(8895)
Slot#26 0x2320(8992)~0x233F(9023)
Slot#28 0x2360(9056)~0x237F(9087)
Slot#30 0x23A0(9120)~0x23BF(9151)
Slot#34 0x2420(9248)~0x243F(9279)