SUN2000-(50KTL-ZHM3, 50KTL-M3)
User Manual
ID
Name
2002
DC arc
fault
2003
DC arc
fault
2011
String
reverse
connecti
on
2012
String
current
backfeed
Issue 03 (2022-08-30)
Severity
Cause
Major
The PV string power cables
arc or are in poor contact.
● Cause ID 1: PV strings 1
and 2
● Cause ID 2: PV strings 3
and 4
● Cause ID 3: PV strings 5
and 6
● Cause ID 4: PV strings 7
and 8
Major
The PV string power cables
arc or are in poor contact.
Cause ID 1–8: PV strings 1–
8
Major
The PV string polarity is
reversed.
Cause ID 1–8: PV strings 1–
8
Warning
The number of PV modules
connected in series to the
PV string is insufficient. As
a result, the terminal
voltage is lower than that
of other strings.
Cause ID 1–8: PV strings 1–
8
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Solution
Check whether the PV string
cables arc or are in poor contact.
Check whether the PV string
cables arc or are in poor contact.
1. Check whether the PV string
is connected to the device in
reverse polarity. If yes, wait
until the PV string current
decreases to below 0.5 A, set
DC SWITCH to OFF, and
adjust the PV string polarity.
2. If the fault persists, reset the
device on the local
maintenance app or WebUI
of the upper-layer controller.
Alternatively, you can turn off
the AC and DC switches, wait
for 5 minutes, and then turn
on the AC and DC switches.
1. Check whether the number of
PV modules connected in
series to the PV string is less
than that of other PV strings.
If yes, wait until the PV string
current drops below 0.5 A,
turn off all DC switches, and
adjust the number of PV
modules in the PV string.
2. Check whether the open-
circuit voltage of the PV
string is abnormal.
3. Check whether the PV string
is shaded.