MAINTENANCE AND INSPECTION OF A
REDUNDANT SYSTEM
This chapter describes the maintenance and inspection of a redundant system.
35.1

Module Replacement in a Redundant System

Overview
■Replacing a module on the main base unit of the control system
• A module can be replaced by turning on SM1646 (System switching by a user) to execute system switching and powering
off the main base unit in the standby system after system switching.
• A module supporting the online module change function can be replaced by online module change.
■Replacing a module on the main base unit of the standby system
• A module can be replaced by powering off the main base unit of the standby system.
• In a redundant system without extension base units, a module supporting the online module change function can be
replaced by online module change. (In a redundant system with redundant extension base unit, a module on the main base
unit of the standby system cannot be replaced by online module change.)
■Replacing a module on an extension base unit
• A module supporting the online module change function can be replaced by online module change.
• When replacing a module not supporting the online module change function, power off both systems before replacing.
Replacement of each module
The following table lists modules and whether each module can be replaced.
: Replaceable, : Not replaceable, : Inapplicable
Replacement
Availability
target
Redundant system without
extension base units
Module on the
main base unit
of the control
system
While power is
on
CPU module
Power supply
module
Redundant power
supply module
Redundant function
module
I/O module
Intelligent function
module
35 MAINTENANCE AND INSPECTION OF A REDUNDANT SYSTEM
540
35.1 Module Replacement in a Redundant System
Module on the main
base unit of the
standby system
After
While
powered
power is
off
on
*2
*2
*1
*3*4
Redundant system with redundant extension
base unit
Module on the
Module on the main
main base unit
base unit of the
of the control
standby system
system
While power is
After
on
powered
off
*2
*2
*1
*1
*3
*3*4
Reference
Module
on an
extension
base unit
While
While
power is
power is
on
on
Page 542 Replacing the
CPU module
Page 544 Replacing the
power supply module
*1
*1
Page 544 Replacing the
redundant power supply
module
Page 545 Replacing the
redundant function
module
Page 545 Replacing the
I/O module
*3
Page 546 Replacing the
intelligent function
module