Battery; Figure 5-3: Coin Cell Battery - GE Kelman MINITRANS User Manual

Transformer oil dissolved gas and moisture monitor
Hide thumbs Also See for Kelman MINITRANS:
Table of Contents

Advertisement

 Relay 2 notifies the user when a user-configurable caution and/or alarm threshold
is reached.
 The red LED indicates a caution and/or alarm state. Flashing denotes a caution
state whereas continuous illumination denotes an alarm state. If after the next
measurement run, no alarm or caution states exist, the red LED switches off. Use
the TransConnect software to set alarm and caution limits for many different
combinations of results. (See the TransConnect user guide for more information).

5.3 Battery

The product uses a non-rechargeable lithium coin cell battery (Panasonic CR2450 3 V 620
mAh) as shown in Figure 5—3. In the event that the battery needs to be replaced, data
from the product must be backed up. Failure to do so may result in historical data loss.
The following steps describe how to change the battery:
1. Back up the product data – contact your GE representative.
2. Open the inner door to locate the battery on the system board (as
shown in Figure 5—3).
3. Slide the battery out of its housing.
4. Replace with a new Panasonic CR2450 3 V 620 mAh coin cell.
5. Close the inner door.
There is a danger of a new battery exploding if installed incorrectly.
Dispose of the used battery in accordance with local regulations — not in a fire
or with household waste. Contact your local waste disposal agency for the
address of the nearest battery deposit site. Perchlorate material — special
handling may apply. See:
MA-006- MINITRANS User Guide - Rev 2.1
Figure 5—3: Coin cell battery
www.dtsc.ca.gov/hazardouswaste/perchlorate/
13-Oct-15
Page 10 of 25