10. How to connect and configure a Run Forward or

Run Reverse switch

The procedure described in section 7 enables
Run/Stop operation via the red and green
buttons on the Inverter keypad.
If this is unsuitable for the application, a remote
switch can be used instead.
10.1 Parameters to change for remote Run/Stop
Parameter Description
Pr. 2
Minimum Speed
Pr. 178
STF terminal function selection
Pr. 179
STR terminal function selection
Pr. 250
Stop Selection
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright
Drive Supermarket and must not be reproduced or altered without prior written permission.
How to set
Set to
5.00
Set to
60
Set to
61
Set to
9999
2 3 1
1 3
2
R
Switch, 3 Position
Normally Open
"Run Forward / Stop / Run Reverse"
This section explains how to enable 2-wire
control with Run Forward / Stop / Run Reverse
commands via a single selector switch.
The Inverter must be in "EXT" control mode to
operate from the I/O terminals. Press PU/EXT
to select.
to run the motor at 5Hz if no other speed reference has been defined.
for forward rotation selection. This is the factory default.
for reverse rotation selection. This is the factory default.
for Run Forward, Run Reverse. This is the factory default.
10.2 Connecting the Switch
A wiring diagram is shown in the illustration
opposite.
The PC terminal is a common connection for
terminals RL, RM, RH, STF and STR when the
jumpers are set in "Source" (the default). If the
jumpers have been changed to "Sink", use SD
as the common instead.
A suitable 3 position NO (Normally Open)
switch should be installed between terminals
PC, STF and STR. The centre position should
remain open circuit.
When a connection is made between terminals
PC and STF, the motor will run forward. When
terminals PC and STR are connected, the
motor will run in reverse.
If terminals STF and STR are connected to PC
F
at the same time the motor will stop.
The Inverter must be in external control mode to
operate in 3-wire control. Check that the "EXT"
indicator is illuminated to confirm. The PU/EXT key
can be used to change the mode if required.
©
The Inverter