(Optional) Installing T/H Sensors Outside Cabinets
5.4
1. Connect the temperature and humidity (T/H) sensor cable (W12).
2. Set the DIP switches on the T/H sensors.
Name
Return air 2 temp/humid
Cold aisle 1 temp/humid
Cold aisle 2 temp/humid
Cold aisle 3 temp/humid
Cold aisle 4 temp/humid
Cold aisle 5 temp/humid
Hot aisle 1 temp/humid
Hot aisle 2 temp/humid
Hot aisle 3 temp/humid
Hot aisle 4 temp/humid
Hot aisle 5 temp/humid
(Optional) Connecting the Teamwork Network Cable
5.5
The smart cooling product supports both FE teamwork networking and CAN teamwork
networking (hand-in-hand).
All smart cooling products in a
teamwork group must be of the
same model.
Do not directly connect the first and
the last smart cooling products to
form a ring network.
A maximum of 32 smart cooling
products can be networked in one
group. The teamwork cable between
two adjacent smart cooling products
must not exceed 10 m.
If CAN networking is required onsite,
set Enable teamwork CAN resistor
for the first and last smart cooling
products to Yes on the screen.
Address
1
1
ON
11
ON
12
OFF
13
ON
14
OFF
15
ON
21
ON
22
OFF
23
ON
OFF
24
ON
25
Connecting an FE teamwork network cable
9
The T/H sensors inside the cabinet are
secured at the return air side and their IN
ports are connected to the main control
board. When connecting the T/H sensors
outside the cabinet, connect the OUT port
of one T/H sensor inside the cabinet to the
IN port of the next T/H sensor outside the
cabinet. Connect all T/H sensors in series
in this way.
T/H sensors in the aisle should be installed
at the door frame inside the server cabinet
and 1.5 m above the ground (33 U). After
they are secured, set the sensor positions
based on their location and the table.
DIP Switch ID
2
3
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
4
5
6
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF