Performance data and behavior in operation
5.3 Characteristic data of the DP interface / DP slave
Characteristic
Size of the DP data
areas
Min. slave interval
SYNC / FREEZE
User parameter assignment data
User diagnostics data
NOTICE
Fail-safe
Fail-safe mode is possible only if you use the GSD files listed in the table above.
Execution times of the program blocks for PROFIBUS DP
The following table will help you to calculate the CPU cycle times (OB1) in DP slave mode.
The table contains the execution time of the FCs (FC DP_SEND, FC DP_RECV) required for
DP processing on the S7-300 / C7-300 CPU.
Component
Execution time on the CPU
314C-2DP (6ES7 314-6CF00-
0AB0)
Execution time on the CPU 317-
2PN/DP (6ES7 317-2EJ10-
0AB0)
26
CP 342-5 (6GK7 342-5DA03-0XE0)
CP 342-5 FO(6GK7 342-5DF00-0XE0)
You will find the GSD files on the Internet under the following entry ID:
113652 (http://support.automation.siemens.com/WW/view/en/113652)
DP input area
DP output area
CP 342-5 (6GK7 342-5DA03-0XE0)
CP 342-5 FO(6GK7 342-5DF00-0XE0)
Explanation / values
Per DP_SEND block call:
<3.0 ms at 8 bytes
<5.0 ms at 240 bytes
Per DP_SEND block call:
<1.5 ms at 8 bytes
<2.3 ms at 240 bytes
Explanation / values
SI0180D6.GSD
SIEM80D7.GSD
240 bytes max.
240 bytes max.
0.6 ms
Is supported
The following is not supported
3 bytes; value: 40 00 00 (fixed)
0 bytes
Per DP_RECV block call:
<3.3 ms at 8 bytes
<5.8 ms at 240 bytes
Per DP_RECV block call:
<1.7 ms at 8 bytes
<2.8 ms at 240 bytes
CP 342-5 / CP 342-5 FO
Manual, 10/2011, C79000-G8976-C146-09