SUN2000-(100KTL, 110KTL, 115KTL)-M2
User Manual
No.
Indicator
2
Grid connection
indicator
3
Communications
indicator
4
Alarm/
Maintenance
indicator
Issue 02 (2022-06-30)
Status (Blinking Fast: On for 0.2s
and Off for 0.2s; Blinking Slowly:
On for 1s and Off for 1s)
Blinking green fast
Off
Steady green
Blinking green fast
Off
Blinking green fast
Off
Alarm status
Steady red
Blinking red fast
Copyright © Huawei Technologies Co., Ltd.
Description
If the alarm/maintenance
indicator is red, an
environmental fault at the DC
side of the solar inverter is
generated.
The solar inverter disconnects
from all PV strings, or the DC
input voltage of all MPPT
circuits is less than 200 V.
The solar inverter is in grid-
tied mode.
If the alarm/maintenance
indicator is red, an
environmental fault at the AC
side of the solar inverter is
generated.
The solar inverter is not in
grid-tied mode.
The solar inverter receives
communication data
normally.
The solar inverter has not
received communication data
for 10 seconds.
A major alarm is generated.
● If the PV connection
indicator or grid
connection indicator is
blinking green fast,
troubleshoot DC or AC
environmental faults as
instructed by the SUN2000
app.
● If the PV connection
indicator and grid
connection indicator are
both not blinking green
fast, replace components
or the solar inverter as
instructed by the SUN2000
app.
A minor alarm is generated.
2 Overview
15