Panasonic GT32-R User Manual page 134

Programmable display
Table of Contents

Advertisement

Code No.
Content
General-purpose
**1025
memory shortage
**1027
Remote mode error
**102D
Forced operation error
**1040
**1041
The record area for
logging was
**1042
overwritten.
**1044
SD memory card
**1043
writing error
The record area for
logging cannot be
**1045
reserved in the
SRAM.
**10A0
FROM write error
Ethernet IP address
**1100
setting error
Ethernet subnet mask
**1101
setting error
Ethernet default
**1102
gateway setting error
Ethernet port number
**1103
setting error
Index register value
**1060
error
Start time device
**1080
value error
Connected GT
designation area error
The bit corresponding
**2000
to the connected GT
in the connected GT
designation area.
5-12
Cause and solution
General-purpose memory shortage in the destination PLC.
The PLC (FP2/FP2SH) is set to the RUN mode. Change to the
REMOTE mode or PROG. mode.
Check if a device that cannot be forcibly operated in the PROG.
mode has been forcibly turned on or off.
A SD memory card is not inserted.
Check the SD memory card slot.
Data cannot be written into the SD memory card. Check whether
the SD memory card is not write-protected.
As the memory of the SD memory card has been exhausted.
Delete some data in the SD memory card or prepare a new SD
memory card.
The setting to stop writing to SD memory card has been set.
Cancel the writing stop setting.
The setting to stop writing to SD memory card has been set.
Cancel the writing stop setting.
Transfer all data.
The firmware file loaded from a SD card is damaged.
Recreate the file in the SD card.
The IP address for Ethernet is not specified correctly. Check the
IP address for the GT.
The subnet mask for Ethernet is not specified correctly. Check
the subnet mask for the GT.
The default gateway for Ethernet is not specified correctly.
Check the default gateway for the GT.
The port number for Ethernet is not specified correctly. Check
the port number error for the GT.
The device value for index modifier is out of the setting range.
Check the setting value.
The value at the start of the line graph function is out of the
setting range. Check the setting value.
The bit in the connected GT designation area corresponding to
the station number of the connected GT is not on.
Check the connected GT designation area.