Huawei UPS5000-H-400 kVA User Manual page 163

Hide thumbs Also See for UPS5000-H-400 kVA:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Module)
EMC Test Item
Impact current (lightning protection)
Voltage dips and short interruptions
(220 V AC)
Power frequency magnetic field
Table 11-5 Mains input electrical specifications
Item
Power
system
Rated
voltage
Voltage
range
Rated
frequency
Frequency
range
Power factor
Harmonic
current
Issue 02 (2021-04-22)
400kVA/500kVA/600kVA/800kVA
Three-phase four-wire + PE
380 V AC/400 V AC/415 V AC (line voltage)
380 V/400 V/415 V
0–30°C: not derated at 323–485 V, derated from 100% load to
45% load at 323–191 V, and derated from 45% load to 35%
load at 191–138 V
30–40°C: not derated at 342–485 V, derated from 100% load to
45% load at 342–191 V, and derated from 45% load to 35%
load at 191–138 V
50 Hz/60 Hz
40–70 Hz
● > 0.99 (100% load)
● > 0.98 (50% load)
● > 0.94 (30% load)
● THDi < 9% (30% linear load), THDi < 6% (50% linear load),
THDi < 3% (100% linear load)
● THDi < 11% (30% non-linear load), THDi < 8% (50% non-
linear load), THDi < 5% (100% non-linear load)
Remarks:
1. The preceding specifications are met when the mains input
and bypass input share a power source.
2. The input THDu is less than 2%.
Copyright © Huawei Technologies Co., Ltd.
11 Technical Specifications
Standard
If a surge protection box is configured:
5 kA (common mode), criterion B
IEC 61000-4-11
IEC 61000-4-8
155