Ground insulation
Isolation Failure
impedance of PV
string is too low
Ground leakage
Ground Failure
current is too high
Relay Check
Self checking of
Failure
relay failure
DC Injection
/
High
EEPROM R/W
/
Failure
Internal
SPI Failure
communication
failure
DC Bus High
BUS voltage is
over-high
Isolation failure
1. Use multi-meter to check if the
could be caused by
resistance between earth & inverter
multiple reasons
frame is close to zero. If it's not, please
like that the PV
ensure that the connection is well.
panels are not
2. If the humidity is too high, isolation
grounded well, DC
failure may occur.
cable is broken, PV
3. Check the resistance between PV1+/
panels are aged
PV2+/PV3+/PV4/+BAT+/PV- to earth.
or surrounding
If the resistance is lower than the
humidity is
minimum isolation resistance shown in
comparatively
the table( chapter 2.4.2 ) , check the
heavy, etc.
system wiring connection.
4. Try to restart the inverter. Check if
the fault still occurs. If not, it means it
is caused by an occasional situation, or
contact technical support.
Ground failure
Check (use multi-meter) if there is
could be caused by
voltage (normally should be close to
multiple reasons
0V) between earth & inverter frame. If
like that the
there is a voltage, it means the neutral
neutral cable on
& ground cables are not connected well
the AC side is not
on the AC side. If it happens only in the
connected well or
early morning/dawn /rainy days with
the surrounding
higher air humidity and is recovered
humidity is
soon, it should be normal.
comparatively
heavy, etc.
Neutral & ground
Check (use multi-meter) if there is high
cables are not
voltage (normally should be lower than
connected well on
10V) between N & PE cable on the AC
AC side or just an
side. If the voltage is higher than 10V,
occasional failure
it means the Neutral & ground cable
are not connected well on AC side or
restart inverter.
The inverter
Try to restart the inverter, check
detects a higher
if it still occurs. If not, it is just an
DC component in
occasional situation. Otherwise,
AC output
contact technical support immediately.
Caused by a strong
Try to restart the inverter, check
external magnetic
if it still occurs. If not, it is just an
field etc.
occasional situation. Otherwise,
contact technical support immediately.
Caused by a strong
Try to restart the inverter, check
external magnetic
if it still occurs. If not, it is just an
field etc.
occasional situation. Otherwise,
contact technical support immediately.
/
Try to restart the inverter. Check if the
fault still occurs. If not, it means it is
caused by an occasional situation, or
contact technical support.