LG multi V ARUN Series Installation Manual page 81

Hide thumbs Also See for multi V ARUN Series:
Table of Contents

Advertisement

u The Procedure of Automatic Addressing
Power On
Waiting 3 minutes
Press RED Button for 5 sec.
(H/P : SW0B, C/O : SW02V)
7-segment LED
Don't press RED Button
(H/P : SW0B, C/O : SW02V)
Waiting about 2~7 minutes
7-segment LED
= 88
YES
OK
Auto addressing start
= 88
• Auto addressing setting end
Numbers of indoor unit connection set whose
addressing is completed are indicated for 30seconds
on 7-segment LED after completing setting
NO
Indoor address number is displayed on wired remote control or
indoor unit display window. It is not an error message, will
disappeared when on/off button is pressed on remote control
ex) Display of 01, 02, ..., 15 means connection of 15 indoor
units and auto addressing is completed normally.
Electrical Wiring
Check the connections
of transmission line
Installation Manual 81