2 Engineering
2.2.2

Configuring the SIMATIC RTU3041C

This section shows you all necessary steps to configure the RTU3041C for the
application described here.
Note
The supplied project
"109739240_RTU3041C_TCSB_SINEMA_RC_PROJ_V30.zip" contains the
complete configuration file ("*.cfg"), which you can load into your RTU3041C and
modify for your application in just a few steps (see
This section is for information only.
Note
Insert a SIM card into the RTU3041C before configuring.
For each RTU, you need a SIM card with data option. You can obtain this from
your mobile provider.
General configuration
1. Connect the RTU3041C to your "Engineering Station 1" via a network cable.
Note
If you are using multiple RTUs, address conflicts may occur during initial startup
because each RTU is assigned the same IP address by default. Therefore, during
commissioning, ensure that only one RTU is connected to your network at a time.
2. If necessary, change the IP address of your "Engineering PG/PC"
(in accordance with
subnet.
3. Start up the RTU3041C by briefly pressing the WKUP/RESET button on the
RTU.
4. In a browser, open the web server of the RTU3041C at the address
"192.168.0.3".
Securely Connecting RTU3041C to TeleControl Server Basic
Entry ID: 109739240,
V3.0,
Table 2-1
) so that it and the RTU3041C are on the same
07/2021
Section
2.2.5).
24