From the previous page
Set the number of sending bytes of the master station register link [DCM (decimal), word]
• Set the number of sending bytes in decimal on the parameter addresses 005200 to 005201
• These top addresses should not overlap the relay link area or the flag area, or exceed the setting
value (0 to 2048 bytes for each station, 2048 bytes for all stations in total).
(In case of setting 16 bytes using JW-13PG: Example of page 9·41)
Set the number of sending bytes of the slave station (01 to 77
• Set the number of sending bytes in decimal on the parameter addresses 005202 to 005377
(set in each station, 2 bytes for each station).
These top addresses should not overlap the resister link area, or the flag area, or exceed the
setting range (0 to 2048 bytes for each station, 2048 bytes for all stations in total).
Slave
station 01
Slave
station 77
9
(In case of setting 8 bytes both for slave station 01 and 02: example of page 9·41)
Slave station 01
Slave station 02
To the next page
Lower
005200
(8)
Upper
005201
(8)
Display the contents of parameter addresses 005200 to
005201
Write 00016
in decimal notation.
(D)
Lower
005202
(8)
Upper
005203
(8)
to
to
Lower
005376
(8)
Upper
005377
(8)
(8)
Enter by decimal
(8)
Screen display of JW-13PG
) register link [DCM (decimal), word]
(8)
Write 00008
in parameter
(D)
addresses 005202 to 005203
Write 00008(D) in parameter
addresses 005204 to 005205
9
46
·
05174
D
00000
05176
D
00000
I PARAM.
>05200
D
00016
.
(8)
.
(8)
Screen display of JW-13PG
05200
D
00016
05202
D
00008
I PARAM.
>05204
D
00008
.
(8)
.
(8)