6. Functional description

6.1. Manual call point

Manual call point and stop device: In the event of an alarm, the glass pane (2) is broken
first, then the manual call point (3) is pressed hard.
This activates the microswitch for alarm triggering and the indicator LED (4) flashes.
A locking mechanism holds the pressed push button down.
The pressed push button is reset by manually activating the reset lever (5) or by opening
the detector door (1) ⇒ The alarm is reset and the display LED goes out (4).
1
2
3

6.2. Single action call point

With single action call points, the alarm is triggered when the glass pane (2) is broken and
the button (3) springs up.
This activates the microswitch for alarm triggering and the display LED (4) flashes.
After a new glass pane (2) has been inserted, the call point (3) is reset by opening the
detector doors (1).

6.3. Functional test

Manual call point and stop device: To trigger the alarm, press the manual call point (3)
hard. The display LED (4) flashes. Use the reset lever (5) to return the manual call point to
the starting status.
Single action call point: To trigger the alarm, open the detector door (1). The display LED
(4) flashes. To reset the single action call point to its starting status, close the detector
door (1).

7. Installation

D The non−automatic fire detector is designed for wall mounting.
D The installation height, according to VdS regulations, is 1400 mm (± 200 mm) from the
floor to the centre of the push button.
D The connection cables can be surface or flush−mounted.
D The cable ducting should be carried out using the intended openings in the housing
(see 7.2 Cable duct).
D The installation location is to be selected so that approximately 38 mm space remains
free on the right−hand side for opening the door.
5
4
3
Page 9 of 17
PI − 34.53 en
1
2
BDL−F.01U.066.176
A2.en/ 11.04.2007
ST−FIR/ PRM1 / sib