Maintenance to be performed by the installer or the maintenance company
Quarterly
Yearly
FP400 Series Installation Manual
4 M
Maintenance measures recommended in EN54-14 must be adopted.
Inspect the entries in the on-site register and the records of the control panel.
Implement the appropriate corrective action.
Check all battery connections and the battery voltages.
In every zone, check the alarm, faults and all auxiliary functions of the control and
signalling equipment.
Visually inspect the control and signalling equipment to detect any possible increase
in humidity and/or any other type of deterioration.
Check if there has been any structural alteration to the site that may affect the
functioning of the detectors, manual call points or sounders. If so, take the
appropriate action.
Any failure must be noted down in the on-site register book and the corrective action
taken as soon as possible.
Place the control panel in "Test" and check the configuration of the system. Check
that all the detectors and manual call points work according to the manufacturer's
specifications and programmed requirements.
Visually inspect all the equipment connections and make sure that they are securely
fastened, that they have not been damaged and that they are appropriately protected.
Examine and test all batteries.
Any defect must be noted down in the on-site register and the corrective action taken
as soon as possible