78
PCS100 AVC-20 User Manual
Code
Origin
Type
331
M
W
332
M
W
404
R,I
F
GDM Info
Description
SCM fault
The System Configuration
Module (SCM) has detected
a fault in the SCM or the
System.
Master Reset
The Master has performed a
software reset.
IGBT Gate
IGBT desaturation detected
drive Failure
without the IGBT being
switched.
Table 9-2: PCS100 AVC-20 Event codes and descriptions
Recommended Action
See document
2UCD200000E430 PCS100
SCM Diagnostics.
Info only. Caused by a
software lock up or system
reboot.
Power down and restart. If the
fault is not resolved contact
your ABB Service Agent to
have relevant module replaced.