Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
Page 9
LD0.MAPGAPC2 Multipurpose analog protection function (2)................36 LD0.MAPGAPC3 Multipurpose analog protection function (3)................36 LD0.MAPGAPC4 Multipurpose analog protection function (4)................37 LD0.MAPGAPC5 Multipurpose analog protection function (5)................37 LD0.MAPGAPC6 Multipurpose analog protection function (6)................37 LD0.MAPGAPC7 Multipurpose analog protection function (7)................37 REM620 Point List Manual...
Page 10
CTRL.CBCSWI2 Circuit breaker control .......47 CTRL.DCCSWI1 Controllable disconnector (1) control ..47 CTRL.DCCSWI2 Controllable disconnector (2) control..47 CTRL.DCCSWI3 Controllable disconnector (3) control..47 CTRL.DCCSWI4 Controllable disconnector (4) control..48 CTRL.ESCSWI1 Controllable earth switch (1) control ..48 CTRL.ESCSWI2 Controllable earth switch (2) control ..48 REM620 Point List Manual...
Page 11
CTRL.DCXSWI3 Controllable disconnector 3, 4-pole (2 bit) position values..............56 CTRL.DCXSWI4 Controllable disconnector 4, 4-pole (2 bit) position values..............56 CTRL.ESSXSWI1 Earth switch 1, 4-pole (2 bit) position values..................57 CTRL.ESSXSWI2 Earth switch 2, 4-pole (2 bit) position values..................57 REM620 Point List Manual...
Page 12
Protection related functions............61 DR.RDRE1 Disturbance recorder values.......61 LD0.SECRSYN1 Synchrocheck line and bus state....61 Physical and raw I/O data............62 LD0.XRGGIO105 RTD inputs..........62 LD0.XRGGIO110 RTD inputs..........62 Section 3 DNP3 protocol implementation........63 DNP3 device profile................63 DNP3 implementation table..............65 Section 4 Glossary.................69 REM620 Point List Manual...
The engineering manual contains instructions on how to engineer the IEDs using the different tools in PCM600. The manual provides instructions on how to set up a PCM600 project and insert IEDs to the project structure. The manual also REM620 Point List Manual...
1.3.2 Document revision history Document revision/date Product version History A/2013-05-07 First release Download the latest documents from the ABB Website http://www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID DNP3 Communication Protocol Manual 1MRS757646 Symbols and conventions 1.4.1...
Parameter values are indicated with quotation marks. The corresponding parameter values are "On" and "Off". • IED input/output messages and monitored data names are shown in Courier font. When the function starts, the START output is set to TRUE. REM620 Point List Manual...
Page 17
3 Multipurpose analog protection, MAPGAPC4 MAP (4) MAP (4) instance 4 Multipurpose analog protection, MAPGAPC5 MAP (5) MAP (5) instance 5 Multipurpose analog protection, MAPGAPC6 MAP (6) MAP (6) instance 6 Table continues on next page REM620 Point List Manual...
Page 18
TCM (1) Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2) Current circuit supervision, instance 1 CCRDIF1 MCS 3I (1) CSM 3I (1) Fuse failure supervision SEQRFUF1 FUSEF (1) 60 (1) Table continues on next page REM620 Point List Manual...
Page 19
Time delay on (8 pcs), instance 1 TONGAPC1 TON (1) TON (1) Time delay on (8 pcs), instance 2 TONGAPC2 TON (2) TON (2) Time delay on (8 pcs), instance 3 TONGAPC3 TON (3) TON (3) Table continues on next page REM620 Point List Manual...
Page 20
FKEYGGIO1 FKEY (1) FKEY (1) Logging functions Disturbance recorder RDRE1 DR (1) DFR (1) Fault recorder FLTMSTA1 FR (1) FR (1) Sequence event recorder SER1 SER (1) SER (1) Load profile LDPMSTA1 LOADPROF (1) LOADPROF (1) REM620 Point List Manual...
This list represents the superset of DNP3 points. The actual set of available points, meaning the actual set of available applications, is determined by the IED's order code. Supported functions Table 2: Supported functions in REM620 Function block ME201 PHLPTOC1 ●...
IEC 61850 name SA name Description Values CTRL.LLN0 .Loc.stVal Remote/Local state 0/1=Rem/Loc 2.3.1.2 LD0.LLN0 Settings supervision Table 5: LD0.LLN0 Settings supervision IEC 61850 name SA name Description Values LD0.LLN0 .SetChg.stVal Settings changed 1=Changed .SetSeld.stVal Settings reserved 1=Reserved REM620 Point List Manual...
.LoWrn.stVal LOW_WARN Low warning 1=Warning 2.3.4.3 LD0.RESCMMXU1 Residual current limit supervision Table 24: LD0.RESCMMXU1 Residual current limit supervision IEC 61850 name SA name Description Values LD0.RESCMMXU1 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm .HiWrn.stVal HIGH_WARN High warning 1=Warning REM620 Point List Manual...
-phsB Start 1=Start .Str.phsC -phsC Start 1=Start 2.3.5.2 LD0.TRPPTRC1 Global conditioning (1) Table 28: LD0.TRPPTRC1 Global conditioning (1) IEC 61850 name SA name Description Values LD0.TRPPTRC1 .Op.general Operate input signal 1=Operate .Tr.general Trip output signal 1=Trip REM620 Point List Manual...
.Str.general START Stage start 1=Start 2.3.5.41 LD0.LOFLPTUC2 Loss of load protection Table 67: LD0.LOFLPTUC2 Loss of load protection IEC 61850 name SA name Description Values LD0.LOFLPTUC2 .Op.general OPERATE Stage operate 1=Operate .Str.general START Stage start 1=Start REM620 Point List Manual...
2.3.6.4 LD0.SECRSYN1 Synchrocheck Table 71: LD0.SECRSYN1 Synchrocheck IEC 61850 name SA name Description Values LD0.SECRSYN1 .SynPrg.stVal SYNC_INPRO Synch in progress 1=In progress .FailCmd.stVal CMD_FAIL_AL CB close request failed 1=Failed .FailSyn.stVal CL_FAIL_AL CB close command failed 1=Failed REM620 Point List Manual...
LD0.MAPGAPC3 Multipurpose analog protection function (3) Table 76: LD0.MAPGAPC3 Multipurpose analog protection function (3) IEC 61850 name SA name Description Values LD0.MAPGAPC3 .Op.general OPERATE Stage operate 1 = Operate .Str.general START Stage start 1 = Start REM620 Point List Manual...
LD0.MAPGAPC8 Multipurpose analog protection function (8) Table 81: LD0.MAPGAPC8 Multipurpose analog protection function (8) IEC 61850 name SA name Description Values LD0.MAPGAPC8 .Op.general OPERATE Stage operate 1 = Operate .Str.general START Stage start 1 = Start REM620 Point List Manual...
LD0.MVGAPC1 Multipurpose binary inputs (1) Table 86: LD0.MVGAPC1 Multipurpose binary inputs (1) IEC 61850 name SA name Description Values LD0.MVGAPC1 .Q1.stVal Input 1 signal 0/1=Off/On .Q2.stVal Input 2 signal 0/1=Off/On .Q3.stVal Input 3 signal 0/1=Off/On Table continues on next page REM620 Point List Manual...
0/1=Off/On .Q2.stVal Input 2 signal 0/1=Off/On .Q3.stVal Input 3 signal 0/1=Off/On .Q4.stVal Input 4 signal 0/1=Off/On .Q5.stVal Input 5 signal 0/1=Off/On .Q6.stVal Input 6 signal 0/1=Off/On .Q7.stVal Input 7 signal 0/1=Off/On .Q8.stVal Input 8 signal 0/1=Off/On REM620 Point List Manual...
0/1=Off/On .SPCS10.stVal Output 10 state 0/1=Off/On .SPCS11.stVal Output 11 state 0/1=Off/On .SPCS12.stVal Output 12 state 0/1=Off/On .SPCS13.stVal Output 13 state 0/1=Off/On .SPCS14.stVal Output 14 state 0/1=Off/On .SPCS15.stVal Output 15 state 0/1=Off/On .SPCS16.stVal Output 16 state 0/1=Off/On REM620 Point List Manual...
0/1=Off/On .SPCS08.stVal Output 8 state 0/1=Off/On .SPCS09.stVal Output 9 state 0/1=Off/On .SPCS10.stVal Output 10 state 0/1=Off/On .SPCS11.stVal Output 11 state 0/1=Off/On .SPCS12.stVal Output 12 state 0/1=Off/On .SPCS13.stVal Output 13 state 0/1=Off/On Table continues on next page REM620 Point List Manual...
0/1=Off/On .SPCS03.stVal LED 3 state 0/1=Off/On .SPCS04.stVal LED 4 state 0/1=Off/On .SPCS05.stVal LED 5 state 0/1=Off/On .SPCS06.stVal LED 6 state 0/1=Off/On .SPCS07.stVal LED 7 state 0/1=Off/On .SPCS08.stVal LED 8 state 0/1=Off/On Table continues on next page REM620 Point List Manual...
LD0.LLN0/LPHD1 Reset indications and LEDs, reset device Table 104: LD0.LLN0/LPHD1 Reset indications and LEDs, reset device IEC 61850 name SA name Description Type LD0.LLN0 .LEDRs1.Oper.ctlVal Reset indications and LEDs .LEDRs2.Oper.ctlVal Reset alarm LEDs LD0.LPHD1 .RsDev.Oper.ctlVal Reset device REM620 Point List Manual...
IEC 61850 name SA name Description Type CTRL.DCCSWI2 .Pos.Oper.ctlVal Disconnector control On/Off 2.4.2.5 CTRL.DCCSWI3 Controllable disconnector (3) control Table 109: CTRL.DCCSWI3 Controllable disconnector (3) control IEC 61850 name SA name Description Type CTRL.DCCSWI3 .Pos.Oper.ctlVal Disconnector control On/Off REM620 Point List Manual...
LD0.SSCBR1 Reset signals of CB condition monitoring IEC 61850 name SA name Description Type LD0.SSCBR1 .RsAccAPwr.Oper.ctlVal RST_IPOW Reset accum. energy .RsCBWear.Oper.ctlVal RST_CB_WEAR Reset CB life and op. counter .RsSprChaTm.Oper.ctlVal RST_SPR_T Reset spring charge alarm .RsTrvTm.Oper.ctlVal RST_TRV_T Reset travel time alarm REM620 Point List Manual...
The binary outputs can be configured either as pulse- or persistent-type outputs. Pulse- type outputs are triggered with the write value "1". Persistent-type outputs can be written with both values "1" and "0" values. The setting mode "toggled" for local operation corresponds to "persistent" for remote operation. REM620 Point List Manual...
On/Off .SPCS05.ctlVal Output 5 control On/Off .SPCS06.ctlVal Output 6 control On/Off .SPCS07.ctlVal Output 7 control On/Off .SPCS08.ctlVal Output 8 control On/Off .SPCS09.ctlVal Output 9 control On/Off .SPCS10.ctlVal Output 10 control On/Off Table continues on next page REM620 Point List Manual...
The binary outputs can be configured either as pulse- or persistent-type outputs. Pulse- type outputs are triggered with the write value "1". Persistent-type outputs can be written with both values "1" and "0". The setting mode "toggled" for local operation corresponds to "persistent" for remote operation. REM620 Point List Manual...
See the DNP3 communication protocol manual for details. 2.5.1 System functions 2.5.1.1 CTRL.LLN0 Local remote station off Table 124: CTRL.LLN0 Local remote station off IEC 61850 name SA name Description Values Arg 1,2,3,4 CTRL.LLN0 Off=0; Loc=1; Rem=2; .LocRem.stVal Station=3 0…3 0,3,0,3 REM620 Point List Manual...
0,3,0,3 0/1/3=Off/Ok/ .ISCSO7.stVal LED 7 state Alarm 0,3,0,3 0/1/3=Off/Ok/ .ISCSO8.stVal LED 8 state Alarm 0,3,0,3 0/1/3=Off/Ok/ .ISCSO9.stVal LED 9 state Alarm 0,3,0,3 0/1/3=Off/Ok/ .ISCSO10.stVal LED 10 state Alarm 0,3,0,3 0/1/3=Off/Ok/ .ISCSO11.stVal LED 11 state Alarm 0,3,0,3 REM620 Point List Manual...
CTRL.DCSXSWI3 Disconnector 3, 4-pole (2 bit) position values Table 132: CTRL.DCSXSWI3 Disconnector 3, 4-pole (2 bit) position values IEC 61850 name SA name Description Values Arg 1,2,3,4 CTRL.DCSXSWI3 Intermediate=0; Off=1; On=2; .Pos.stVal POSITION Bad=3 0…3 0,3,0,3 REM620 Point List Manual...
-9999…9999 -9999,9999,-9999,9999 .RmnLifPhB.stVal CB_LIFE_B Remaining life, phase B -9999…9999 -9999,9999,-9999,9999 .RmnLifPhC.stVal CB_LIFE_C Remaining life, phase C -9999…9999 -9999,9999,-9999,9999 .TmmsCls.mag.f Close travel time 0…60000 0,60000,0,60000 .TmmsOpn.mag.f Open travel time 0…60000 0,60000,0,60000 .TmsSprCha.mag.f Spring charge time 0…99.99 0,99.99,0,9999 REM620 Point List Manual...
Reverse reactive energy 0…1e10 0,1E10,0,1E10 .SupWh.actVal EA_FWD_ACM Reverse active energy 0…1e10 0,1E10,0,1E10 .TotPF.instMag PF_INST Average power factor -1…1 -1,1,-100,100 .TotW.instMag P_INST Active power 0…999999 0,999999,0,999999 .TotVA.instMag S_INST Apparent power 0…999999 0,999999,0,999999 .TotVAr.instMag Q_INST Reactive power 0…999999 0,999999,0,999999 REM620 Point List Manual...
Rec. memory used 0…100 [%] 0,100,0,100 2.5.6.2 LD0.SECRSYN1 Synchrocheck line and bus state Table 154: LD0.SECRSYN1 Synchrocheck line and bus state IEC 61850 name SA name Description Values Arg 1,2,3,4 LD0.SECRSYN1 .EnSt.stVal Energization state 0…4 0,4,0,4 REM620 Point List Manual...
Implementation table and the point list tables, provides a complete configuration/interoperability guide for communicating with a device. Table 157: Device profile document DNP3 device profile document Vendor name: ABB Oy Device name: REM620 Highest DNP level supported: Device function: For requests: Level 2+ ○...
Page 70
Only non-time-tagged ○ Binary input change with relative time ● Configurable to send one or the other ● Configurable Sends unsolicited responses: Sends static data in unsolicited responses: ● Never ● Never Table continues on next page REM620 Point List Manual...
(non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07 or 08 are responded with qualifiers 00 or 01. Requests sent with qualifiers 17 or 28 are responded with qualifiers 17 or 28. For change-event objects, qualifiers 17 or 28 are always responded. REM620 Point List Manual...
Page 72
17, 28 (index) 32-bit 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) analog 06 (no range, or all) 17, 28 (index) input 07, 08 (limited qty) 17, 28 (index) Table continues on next page REM620 Point List Manual...
Page 73
Time and 129 (response) 07 (limited qty) date CTO 130 (unsol. resp) (qty = 1) Unsynchro 129 (response) 07 (limited qty) nized time 130 (unsol. resp) (qty = 1) and date Table continues on next page REM620 Point List Manual...
Page 74
17 or 28 are always responded.) 3) Writes of internal indications are only supported for index 7 (Restart IIN1-7) 4) Cold and warm restarts return an application layer acknowledge, but no restart action is taken. REM620 Point List Manual...
International Electrotechnical Commission IEC 61850 International standard for substation communication and modeling Intelligent electronic device IET600 Integrated Engineering Toolbox in PCM600 LHMI Local human-machine interface PCM600 Protection and Control IED Manager Select-before-operate WHMI Web human-machine interface REM620 Point List Manual...