Motor protection and control dnp3 point list
Hide thumbs Also See for REM620:
Table of Contents

Advertisement

Quick Links

®
Relion
620 series
Motor Protection and Control
REM620
DNP3 Point List Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB REM620

  • Page 1 ® Relion 620 series Motor Protection and Control REM620 DNP3 Point List Manual...
  • Page 3 Document ID: 1MRS757656 Issued: 2013-05-07 Revision: A Product version: 2.0 © Copyright 2013 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    LD0.ARCSARC1 Fault arc protection stage 1......22 LD0.ARCSARC2 Fault arc protection stage 2......22 LD0.ARCSARC3 Fault arc protection stage 3......22 LD0.SSCBR1 Circuit-breaker condition monitoring....23 LD0.SSCBR2 Circuit-breaker condition monitoring....23 LD0.TCSSCBR1 Trip circuit supervision (1)......23 LD0.TCSSCBR2 Trip circuit supervision (2)......24 REM620 Point List Manual...
  • Page 8 LD0.PHPTUV2 Phase undervoltage protection - stage 2.....................29 LD0.PHPTUV3 Phase undervoltage protection - stage 3.....................29 LD0.ROVPTOV1 Residual overvoltage protection (1)...29 LD0.ROVPTOV2 Residual overvoltage protection (2)...29 LD0.ROVPTOV3 Residual overvoltage protection (3)...30 LD0.MNSPTOC1 Negative-sequence overcurrent protection for motors (1)............30 REM620 Point List Manual...
  • Page 9 LD0.MAPGAPC2 Multipurpose analog protection function (2)................36 LD0.MAPGAPC3 Multipurpose analog protection function (3)................36 LD0.MAPGAPC4 Multipurpose analog protection function (4)................37 LD0.MAPGAPC5 Multipurpose analog protection function (5)................37 LD0.MAPGAPC6 Multipurpose analog protection function (6)................37 LD0.MAPGAPC7 Multipurpose analog protection function (7)................37 REM620 Point List Manual...
  • Page 10 CTRL.CBCSWI2 Circuit breaker control .......47 CTRL.DCCSWI1 Controllable disconnector (1) control ..47 CTRL.DCCSWI2 Controllable disconnector (2) control..47 CTRL.DCCSWI3 Controllable disconnector (3) control..47 CTRL.DCCSWI4 Controllable disconnector (4) control..48 CTRL.ESCSWI1 Controllable earth switch (1) control ..48 CTRL.ESCSWI2 Controllable earth switch (2) control ..48 REM620 Point List Manual...
  • Page 11 CTRL.DCXSWI3 Controllable disconnector 3, 4-pole (2 bit) position values..............56 CTRL.DCXSWI4 Controllable disconnector 4, 4-pole (2 bit) position values..............56 CTRL.ESSXSWI1 Earth switch 1, 4-pole (2 bit) position values..................57 CTRL.ESSXSWI2 Earth switch 2, 4-pole (2 bit) position values..................57 REM620 Point List Manual...
  • Page 12 Protection related functions............61 DR.RDRE1 Disturbance recorder values.......61 LD0.SECRSYN1 Synchrocheck line and bus state....61 Physical and raw I/O data............62 LD0.XRGGIO105 RTD inputs..........62 LD0.XRGGIO110 RTD inputs..........62 Section 3 DNP3 protocol implementation........63 DNP3 device profile................63 DNP3 implementation table..............65 Section 4 Glossary.................69 REM620 Point List Manual...
  • Page 13: Section 1 Introduction

    The engineering manual contains instructions on how to engineer the IEDs using the different tools in PCM600. The manual provides instructions on how to set up a PCM600 project and insert IEDs to the project structure. The manual also REM620 Point List Manual...
  • Page 14: Document Revision History

    1.3.2 Document revision history Document revision/date Product version History A/2013-05-07 First release Download the latest documents from the ABB Website http://www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID DNP3 Communication Protocol Manual 1MRS757646 Symbols and conventions 1.4.1...
  • Page 15: Document Conventions

    Parameter values are indicated with quotation marks. The corresponding parameter values are "On" and "Off". • IED input/output messages and monitored data names are shown in Courier font. When the function starts, the START output is set to TRUE. REM620 Point List Manual...
  • Page 16: Functions, Codes And Symbols

    Section 1 1MRS757656 A Introduction 1.4.3 Functions, codes and symbols Table 1: REM620 functions, codes and symbols Function IEC 61850 IEC 60617 IEC-ANSI Protection Three-phase non-directional overcurrent protection, low stage, PHLPTOC1 3I> (1) 51P-1 (1) instance 1 Three-phase non-directional overcurrent protection, instantaneous PHIPTOC1 3I>>>...
  • Page 17 3 Multipurpose analog protection, MAPGAPC4 MAP (4) MAP (4) instance 4 Multipurpose analog protection, MAPGAPC5 MAP (5) MAP (5) instance 5 Multipurpose analog protection, MAPGAPC6 MAP (6) MAP (6) instance 6 Table continues on next page REM620 Point List Manual...
  • Page 18 TCM (1) Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2) Current circuit supervision, instance 1 CCRDIF1 MCS 3I (1) CSM 3I (1) Fuse failure supervision SEQRFUF1 FUSEF (1) 60 (1) Table continues on next page REM620 Point List Manual...
  • Page 19 Time delay on (8 pcs), instance 1 TONGAPC1 TON (1) TON (1) Time delay on (8 pcs), instance 2 TONGAPC2 TON (2) TON (2) Time delay on (8 pcs), instance 3 TONGAPC3 TON (3) TON (3) Table continues on next page REM620 Point List Manual...
  • Page 20 FKEYGGIO1 FKEY (1) FKEY (1) Logging functions Disturbance recorder RDRE1 DR (1) DFR (1) Fault recorder FLTMSTA1 FR (1) FR (1) Sequence event recorder SER1 SER (1) SER (1) Load profile LDPMSTA1 LOADPROF (1) LOADPROF (1) REM620 Point List Manual...
  • Page 21: Section 2 Dnp3 Data Mappings

    This list represents the superset of DNP3 points. The actual set of available points, meaning the actual set of available applications, is determined by the IED's order code. Supported functions Table 2: Supported functions in REM620 Function block ME201 PHLPTOC1 ●...
  • Page 22 PREVPTOC1 ● MPTTR1 ● MPDIF1 ● CCBRBRF1 ● CCBRBRF2 ● TRPPTRC1 ● TRPPTRC2 ● ARCSARC1 ARCSARC2 ARCSARC3 MAPGAPC1 ● MAPGAPC2 ● MAPGAPC3 ● MAPGAPC4 ● MAPGAPC5 ● MAPGAPC6 ● MAPGAPC7 ● Table continues on next page REM620 Point List Manual...
  • Page 23 ● TCSSCBR1 ● TCSSCBR2 ● CCRDIF1 ● SEQRFUF1 ● MDSOPT1 ● MDSOPT2 ● CMMXU1 ● CMMXU2 ● CSMSQI1 ● RESCMMXU1 ● VMMXU1 ● RESVMMXU1 ● VSMSQI1 ● PEMMXU1 ● LDPMSTA1 ● Table continues on next page REM620 Point List Manual...
  • Page 24: Binary Inputs

    IEC 61850 name SA name Description Values CTRL.LLN0 .Loc.stVal Remote/Local state 0/1=Rem/Loc 2.3.1.2 LD0.LLN0 Settings supervision Table 5: LD0.LLN0 Settings supervision IEC 61850 name SA name Description Values LD0.LLN0 .SetChg.stVal Settings changed 1=Changed .SetSeld.stVal Settings reserved 1=Reserved REM620 Point List Manual...
  • Page 25: Switchgear Functions

    Interlocking bypass 1=Bypassed CTRL.CBCSWI2 .Pos.stSeld SELECTED CB selected 1=Selected CTRL.CBXCBR2 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked CTRL.CCBRBRF2 .OpEx.general TRBU Failure ext.trip 1=Failure .OpIn.general TRRET Operate, re-trip 1=Operate .Str.general CB_FAULT_AL Start, timer running 1=Start REM620 Point List Manual...
  • Page 26: Ctrl.dxxxxx1 Controllable Disconnector (1)

    SA name Description Values CTRL.DCCILO3 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled .ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed CTRL.DCCSWI3 .Pos.stSeld SELECTED CB selected 1=Selected CTRL.DCXSWI3 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked REM620 Point List Manual...
  • Page 27: Ctrl.dxxxxx4 Controllable Disconnector (4)

    SA name Description Values CTRL.ESCILO2 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled .ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed CTRL.ESCSWI2 .Pos.stSeld SELECTED CB selected 1=Selected CTRL.ESXSWI2 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked REM620 Point List Manual...
  • Page 28: Ld0.Emsgapc1 Emergency Start

    OPERATE Operate 1=Operate 2.3.3.3 LD0.ARCSARC3 Fault arc protection stage 3 Table 17: LD0.ARCSARC3 Fault arc protection stage 3 IEC 61850 name SA name Description Values LD0.ARCSARC31 .FADet.stVal ARC_FLT_DET Arc detected 1=Detected LD0.ARCPTRC31 .Op.general OPERATE Operate 1=Operate REM620 Point List Manual...
  • Page 29: Ld0.Sscbr1 Circuit-Breaker Condition Monitoring

    Low pressure lockout 1=Lockout .SprChaAlm.stVal SPR_CHR_ALM Spring charge time alarm 1=Alarm 2.3.3.6 LD0.TCSSCBR1 Trip circuit supervision (1) Table 20: LD0.TCSSCBR1 Trip circuit supervision (1) IEC 61850 name SA name Description Values LD0.TCSSCBR1 .CirAlm.stVal ALARM Supervision alarm 1=Alarm REM620 Point List Manual...
  • Page 30: Ld0.Tcsscbr2 Trip Circuit Supervision (2)

    .LoWrn.stVal LOW_WARN Low warning 1=Warning 2.3.4.3 LD0.RESCMMXU1 Residual current limit supervision Table 24: LD0.RESCMMXU1 Residual current limit supervision IEC 61850 name SA name Description Values LD0.RESCMMXU1 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm .HiWrn.stVal HIGH_WARN High warning 1=Warning REM620 Point List Manual...
  • Page 31: Ld0.Vmmxu1 Three-Phase Voltage Limit Supervision

    -phsB Start 1=Start .Str.phsC -phsC Start 1=Start 2.3.5.2 LD0.TRPPTRC1 Global conditioning (1) Table 28: LD0.TRPPTRC1 Global conditioning (1) IEC 61850 name SA name Description Values LD0.TRPPTRC1 .Op.general Operate input signal 1=Operate .Tr.general Trip output signal 1=Trip REM620 Point List Manual...
  • Page 32: Ld0.Trpptrc2 Global Conditioning (2)

    LD0.DPHHPDOC1 Three-phase directional overcurrent protection - high stage (1) Table 33: LD0.DPHHPDOC1 Three-phase directional overcurrent protection - high stage (1) IEC 61850 name SA name Description Values LD0.DPHHPTOC1 High stage (1) .Op.general OPERATE -Operate 1=Operate .Str.general START -Start 1=Start REM620 Point List Manual...
  • Page 33: Ld0.Dphhpdoc2 Three-Phase Directional Overcurrent Protection - High Stage (2)

    - low stage 1 Table 37: LD0.EFLPTOC1 Non-directional earth-fault and sensitive earth-fault protection - low stage 1 IEC 61850 name SA name Description Values LD0.EFLPTOC1 Low stage (1) .Op.general OPERATE -Operate 1=Operate .Str.general START -Start 1=Start REM620 Point List Manual...
  • Page 34: Ld0.Efhptoc1 Non-Directional Earth-Fault And Sensitive Earth-Fault Protection - High Stage 1

    1=Start 2.3.5.16 LD0.PHPTOV3 Phase overvoltage protection - stage 3 Table 42: LD0.PHPTOV3 Phase overvoltage protection - stage 3 IEC 61850 name SA name Description Values LD0.PHPTOV3 .Op.general OPERATE Stage operate 1=Operate .Str.general START Stage start 1=Start REM620 Point List Manual...
  • Page 35: Ld0.Phptuv1 Phase Undervoltage Protection - Stage 1

    Stage 1 start 1=Start 2.3.5.21 LD0.ROVPTOV2 Residual overvoltage protection (2) Table 47: LD0.ROVPTOV2 Residual overvoltage protection (2) IEC 61850 name SA name Description Values LD0.ROVPTOV2 .Op.general OPERATE Stage 2 operate 1=Operate .Str.general START Stage 2 start 1=Start REM620 Point List Manual...
  • Page 36: Ld0.Rovptov3 Residual Overvoltage Protection (3)

    1=Start 2.3.5.26 LD0.NSPTOV2 Negative-sequence overvoltage protection - stage 2 Table 52: LD0.NSPTOV2 Negative-sequence overvoltage protection - stage 2 IEC 61850 name SA name Description Values LD0.NSPTOV2 .Op.general OPERATE Stage operate 1=Operate .Str.general START Stage start 1=Start REM620 Point List Manual...
  • Page 37: Ld0.Psptuv1 Positive-Sequence Undervoltage Protection - Stage 1

    LD0.FRPFRQ2 Frequency protection (2) IEC 61850 name SA name Description Values LD0.FRPTRC2 .Str.general START Stage start 1=Start LD0.FRPTOF2 Overfrequency .Op.general OPR_OFRQ -Operate 1=Operate LD0.FRPTUF2 Underfrequency .Op.general OPR_UFRQ -Operate 1=Operate LD0.FRPFRC2 Frequency gradient .Op.general OPR_FRG -Operate 1=Operate REM620 Point List Manual...
  • Page 38: Ld0.Frpfrq3 Frequency Protection (3)

    LD0.FRPFRQ5 Frequency protection (5) IEC 61850 name SA name Description Values LD0.FRPTRC5 .Str.general START Stage start 1=Start LD0.FRPTOF5 Overfrequency .Op.general OPR_OFRQ -Operate 1=Operate LD0.FRPTUF5 Underfrequency .Op.general OPR_UFRQ -Operate 1=Operate LD0.FRPFRC5 Frequency gradient .Op.general OPR_FRG -Operate 1=Operate REM620 Point List Manual...
  • Page 39: Ld0.Frpfrq6 Frequency Protection (6)

    2.3.5.37 LD0.MPTTR1 Motor thermal overload protection Table 63: LD0.MPTTR1 Motor thermal overload protection IEC 61850 name SA name Description Values LD0.MPTTR1 .AlmThm.general ALARM Thermal alarm 1=Alarm .Op.general OPERATE Thermal operate 1=Operate .StrInh.general BLK_RESTART Block restart 1=Restart REM620 Point List Manual...
  • Page 40: Ld0.Prevptoc1 Phase Reversal Protection

    .Str.general START Stage start 1=Start 2.3.5.41 LD0.LOFLPTUC2 Loss of load protection Table 67: LD0.LOFLPTUC2 Loss of load protection IEC 61850 name SA name Description Values LD0.LOFLPTUC2 .Op.general OPERATE Stage operate 1=Operate .Str.general START Stage start 1=Start REM620 Point List Manual...
  • Page 41: Protection Related Functions

    2.3.6.4 LD0.SECRSYN1 Synchrocheck Table 71: LD0.SECRSYN1 Synchrocheck IEC 61850 name SA name Description Values LD0.SECRSYN1 .SynPrg.stVal SYNC_INPRO Synch in progress 1=In progress .FailCmd.stVal CMD_FAIL_AL CB close request failed 1=Failed .FailSyn.stVal CL_FAIL_AL CB close command failed 1=Failed REM620 Point List Manual...
  • Page 42: Generic Functions

    LD0.MAPGAPC3 Multipurpose analog protection function (3) Table 76: LD0.MAPGAPC3 Multipurpose analog protection function (3) IEC 61850 name SA name Description Values LD0.MAPGAPC3 .Op.general OPERATE Stage operate 1 = Operate .Str.general START Stage start 1 = Start REM620 Point List Manual...
  • Page 43: Ld0.Mapgapc4 Multipurpose Analog Protection Function (4)

    LD0.MAPGAPC8 Multipurpose analog protection function (8) Table 81: LD0.MAPGAPC8 Multipurpose analog protection function (8) IEC 61850 name SA name Description Values LD0.MAPGAPC8 .Op.general OPERATE Stage operate 1 = Operate .Str.general START Stage start 1 = Start REM620 Point List Manual...
  • Page 44: Ld0.Mapgapc9 Multipurpose Analog Protection Function (9)

    LD0.MVGAPC1 Multipurpose binary inputs (1) Table 86: LD0.MVGAPC1 Multipurpose binary inputs (1) IEC 61850 name SA name Description Values LD0.MVGAPC1 .Q1.stVal Input 1 signal 0/1=Off/On .Q2.stVal Input 2 signal 0/1=Off/On .Q3.stVal Input 3 signal 0/1=Off/On Table continues on next page REM620 Point List Manual...
  • Page 45: Ld0.Mvgapc2 Multipurpose Binary Inputs (2)

    0/1=Off/On .Q2.stVal Input 2 signal 0/1=Off/On .Q3.stVal Input 3 signal 0/1=Off/On .Q4.stVal Input 4 signal 0/1=Off/On .Q5.stVal Input 5 signal 0/1=Off/On .Q6.stVal Input 6 signal 0/1=Off/On .Q7.stVal Input 7 signal 0/1=Off/On .Q8.stVal Input 8 signal 0/1=Off/On REM620 Point List Manual...
  • Page 46: Ld0.Mvgapc4 Multipurpose Binary Inputs (4)

    0/1=Off/On .SPCS10.stVal Output 10 state 0/1=Off/On .SPCS11.stVal Output 11 state 0/1=Off/On .SPCS12.stVal Output 12 state 0/1=Off/On .SPCS13.stVal Output 13 state 0/1=Off/On .SPCS14.stVal Output 14 state 0/1=Off/On .SPCS15.stVal Output 15 state 0/1=Off/On .SPCS16.stVal Output 16 state 0/1=Off/On REM620 Point List Manual...
  • Page 47: Ld0.Spcggio2 Multipurpose Binary Outputs - Status (2)

    0/1=Off/On .SPCS08.stVal Output 8 state 0/1=Off/On .SPCS09.stVal Output 9 state 0/1=Off/On .SPCS10.stVal Output 10 state 0/1=Off/On .SPCS11.stVal Output 11 state 0/1=Off/On .SPCS12.stVal Output 12 state 0/1=Off/On .SPCS13.stVal Output 13 state 0/1=Off/On Table continues on next page REM620 Point List Manual...
  • Page 48: Ld0.Spcrggio1 Multipurpose Binary Outputs - Status (1)

    0/1=Off/On .SPCS03.stVal LED 3 state 0/1=Off/On .SPCS04.stVal LED 4 state 0/1=Off/On .SPCS05.stVal LED 5 state 0/1=Off/On .SPCS06.stVal LED 6 state 0/1=Off/On .SPCS07.stVal LED 7 state 0/1=Off/On .SPCS08.stVal LED 8 state 0/1=Off/On Table continues on next page REM620 Point List Manual...
  • Page 49: Physical And Raw I/O Data

    LD0.XHBGGIO105 Physical I/O IEC 61850 name SA name Description Values LD0.XHBGGIO105 .Ind1.stVal XHB105-Input 1 1/0=ON/OFF .Ind2.stVal XHB105-Input 2 1/0=ON/OFF .Ind3.stVal XHB105-Input 3 1/0=ON/OFF .Ind4.stVal XHB105-Input 4 1/0=ON/OFF .Ind5.stVal XHB105-Input 5 1/0=ON/OFF Table continues on next page REM620 Point List Manual...
  • Page 50: Ld0.Xrggio105 Alarm/Warning

    XRGGIO110 Warning 1=Warning 2.3.8.5 LD0.XAGGIO130 Physical I/O Table 99: LD0.XAGGIO130 Physical I/O IEC 61850 name SA name Description Values LD0.XAGGIO130 .Ind1.stVal X130-Input 1 1/0=ON/OFF .Ind2.stVal X130-Input 2 1/0=ON/OFF .Ind3.stVal X130-Input 3 1/0=ON/OFF .Ind4.stVal X130-Input 4 1/0=ON/OFF REM620 Point List Manual...
  • Page 51: Ld0.Xggio100 Physical I/O

    .Ind4.stVal XB115-Input 4 1/0=ON/OFF .Ind5.stVal XB115-Input 5 1/0=ON/OFF .Ind6.stVal XB115-Input 6 1/0=ON/OFF .Ind7.stVal XB115-Input 7 1/0=ON/OFF .Ind8.stVal XB115-Input 8 1/0=ON/OFF .SPCSO1.stVal XB115-Output 1 1/0=ON/OFF .SPCSO2.stVal XB115-Output 2 1/0=ON/OFF .SPCSO3.stVal XB115-Output 3 1/0=ON/OFF .SPCSO4.stVal XB115-Output 4 1/0=ON/OFF REM620 Point List Manual...
  • Page 52: Binary Outputs

    LD0.LLN0/LPHD1 Reset indications and LEDs, reset device Table 104: LD0.LLN0/LPHD1 Reset indications and LEDs, reset device IEC 61850 name SA name Description Type LD0.LLN0 .LEDRs1.Oper.ctlVal Reset indications and LEDs .LEDRs2.Oper.ctlVal Reset alarm LEDs LD0.LPHD1 .RsDev.Oper.ctlVal Reset device REM620 Point List Manual...
  • Page 53: Switchgear Functions

    IEC 61850 name SA name Description Type CTRL.DCCSWI2 .Pos.Oper.ctlVal Disconnector control On/Off 2.4.2.5 CTRL.DCCSWI3 Controllable disconnector (3) control Table 109: CTRL.DCCSWI3 Controllable disconnector (3) control IEC 61850 name SA name Description Type CTRL.DCCSWI3 .Pos.Oper.ctlVal Disconnector control On/Off REM620 Point List Manual...
  • Page 54: Ctrl.dccswi4 Controllable Disconnector (4) Control

    LD0.SSCBR1 Reset signals of CB condition monitoring IEC 61850 name SA name Description Type LD0.SSCBR1 .RsAccAPwr.Oper.ctlVal RST_IPOW Reset accum. energy .RsCBWear.Oper.ctlVal RST_CB_WEAR Reset CB life and op. counter .RsSprChaTm.Oper.ctlVal RST_SPR_T Reset spring charge alarm .RsTrvTm.Oper.ctlVal RST_TRV_T Reset travel time alarm REM620 Point List Manual...
  • Page 55: Ld0.Sscbr2 Reset Signals Of Cb Condition Monitoring

    The binary outputs can be configured either as pulse- or persistent-type outputs. Pulse- type outputs are triggered with the write value "1". Persistent-type outputs can be written with both values "1" and "0" values. The setting mode "toggled" for local operation corresponds to "persistent" for remote operation. REM620 Point List Manual...
  • Page 56: Ld0.Spcggio2 Multipurpose Binary Outputs (2)

    On/Off .SPCS05.ctlVal Output 5 control On/Off .SPCS06.ctlVal Output 6 control On/Off .SPCS07.ctlVal Output 7 control On/Off .SPCS08.ctlVal Output 8 control On/Off .SPCS09.ctlVal Output 9 control On/Off .SPCS10.ctlVal Output 10 control On/Off Table continues on next page REM620 Point List Manual...
  • Page 57: Ld0.Spcggio3 Multipurpose Binary Outputs (3)

    The binary outputs can be configured either as pulse- or persistent-type outputs. Pulse- type outputs are triggered with the write value "1". Persistent-type outputs can be written with both values "1" and "0". The setting mode "toggled" for local operation corresponds to "persistent" for remote operation. REM620 Point List Manual...
  • Page 58: Ld0.Srgapc1 Multipurpose Binary Outputs - Flip-Flop Resets (1)

    SA name Description Type LD0.SRGAPC1 .Rs1.ctlVal Reset flip-flop 1 .Rs2.ctlVal Reset flip-flop 2 .Rs3.ctlVal Reset flip-flop 3 .Rs4.ctlVal Reset flip-flop 4 .Rs5.ctlVal Reset flip-flop 5 .Rs6.ctlVal Reset flip-flop 6 .Rs7.ctlVal Reset flip-flop 7 .Rs8.ctlVal Reset flip-flop 8 REM620 Point List Manual...
  • Page 59: Ld0.Srgapc2 Multipurpose Binary Outputs - Flip-Flop Resets (2)

    See the DNP3 communication protocol manual for details. 2.5.1 System functions 2.5.1.1 CTRL.LLN0 Local remote station off Table 124: CTRL.LLN0 Local remote station off IEC 61850 name SA name Description Values Arg 1,2,3,4 CTRL.LLN0 Off=0; Loc=1; Rem=2; .LocRem.stVal Station=3 0…3 0,3,0,3 REM620 Point List Manual...
  • Page 60: Ld0.Lphd1 System Values

    0,3,0,3 0/1/3=Off/Ok/ .ISCSO7.stVal LED 7 state Alarm 0,3,0,3 0/1/3=Off/Ok/ .ISCSO8.stVal LED 8 state Alarm 0,3,0,3 0/1/3=Off/Ok/ .ISCSO9.stVal LED 9 state Alarm 0,3,0,3 0/1/3=Off/Ok/ .ISCSO10.stVal LED 10 state Alarm 0,3,0,3 0/1/3=Off/Ok/ .ISCSO11.stVal LED 11 state Alarm 0,3,0,3 REM620 Point List Manual...
  • Page 61: Switchgear Functions

    CTRL.DCSXSWI3 Disconnector 3, 4-pole (2 bit) position values Table 132: CTRL.DCSXSWI3 Disconnector 3, 4-pole (2 bit) position values IEC 61850 name SA name Description Values Arg 1,2,3,4 CTRL.DCSXSWI3 Intermediate=0; Off=1; On=2; .Pos.stVal POSITION Bad=3 0…3 0,3,0,3 REM620 Point List Manual...
  • Page 62: Ctrl.dcsxswi4 Disconnector 4, 4-Pole (2 Bit) Position Values

    CTRL.DCXSWI4 Controllable disconnector 4, 4-pole (2 bit) position values Table 137: CTRL.DCXSWI4 Controllable disconnector 4, 4-pole (2 bit) position values IEC 61850 name SA name Description Values Arg 1,2,3,4 CTRL.DCXSWI4 Intermediate=0; Off=1; On=2; .Pos.stVal POSITION Bad=3 0…3 0,3,0,3 REM620 Point List Manual...
  • Page 63: Ctrl.essxswi1 Earth Switch 1, 4-Pole (2 Bit) Position Values

    CTRL.ESXSWI2 Controllable earth switch 2, 4-pole (2 bit) position values Table 141: CTRL.ESXSWI2 Controllable earth switch 2, 4-pole (2 bit) position values IEC 61850 name SA name Description Values Arg 1,2,3,4 CTRL.ESXSWI2 Intermediate=0; Off=1; On=2; .Pos.stVal POSITION Bad=3 0…3 0,3,0,3 REM620 Point List Manual...
  • Page 64: Sensors And Monitoring Functions

    -9999…9999 -9999,9999,-9999,9999 .RmnLifPhB.stVal CB_LIFE_B Remaining life, phase B -9999…9999 -9999,9999,-9999,9999 .RmnLifPhC.stVal CB_LIFE_C Remaining life, phase C -9999…9999 -9999,9999,-9999,9999 .TmmsCls.mag.f Close travel time 0…60000 0,60000,0,60000 .TmmsOpn.mag.f Open travel time 0…60000 0,60000,0,60000 .TmsSprCha.mag.f Spring charge time 0…99.99 0,99.99,0,9999 REM620 Point List Manual...
  • Page 65: Metering And Measurand Functions

    Description Values Arg 1,2,3,4 LD0.VMMXU1.PhV Phase-to-ground voltage 0.00…4.00 .phsA.cVal.mag U_DB_A -phsA magnitude [xUn] 0,4,0,400 0.00…4.00 .phsB.cVal.mag U_DB_B -phsB magnitude [xUn] 0,4,0,400 0.00…4.00 .phsC.cVal.mag U_DB_C -phsC magnitude [xUn] 0,4,0,400 LD0.VMMXU1.PPV Phase-to-phase voltage Table continues on next page REM620 Point List Manual...
  • Page 66: Ld0.Resvmmxu1 Residual Voltage (1)

    Reverse reactive energy 0…1e10 0,1E10,0,1E10 .SupWh.actVal EA_FWD_ACM Reverse active energy 0…1e10 0,1E10,0,1E10 .TotPF.instMag PF_INST Average power factor -1…1 -1,1,-100,100 .TotW.instMag P_INST Active power 0…999999 0,999999,0,999999 .TotVA.instMag S_INST Apparent power 0…999999 0,999999,0,999999 .TotVAr.instMag Q_INST Reactive power 0…999999 0,999999,0,999999 REM620 Point List Manual...
  • Page 67: Ld0.Fmmxu1 Frequency Measurement

    Rec. memory used 0…100 [%] 0,100,0,100 2.5.6.2 LD0.SECRSYN1 Synchrocheck line and bus state Table 154: LD0.SECRSYN1 Synchrocheck line and bus state IEC 61850 name SA name Description Values Arg 1,2,3,4 LD0.SECRSYN1 .EnSt.stVal Energization state 0…4 0,4,0,4 REM620 Point List Manual...
  • Page 68: Physical And Raw I/O Data

    RTD input 4 10000 -1E4,1E4,-1E4,1E4 -10000… .AnIn5.instMag AI_VAL5 RTD input 5 10000 -1E4,1E4,-1E4,1E4 -10000… .AnIn6.instMag AI_VAL6 RTD input 6 10000 -1E4,1E4,-1E4,1E4 -10000… .AnIn7.instMag AI_VAL7 RTD input 7 10000 -1E4,1E4,-1E4,1E4 -10000… .AnIn8.instMag AI_VAL8 RTD input 8 10000 -1E4,1E4,-1E4,1E4 REM620 Point List Manual...
  • Page 69: Section 3 Dnp3 Protocol Implementation

    Implementation table and the point list tables, provides a complete configuration/interoperability guide for communicating with a device. Table 157: Device profile document DNP3 device profile document Vendor name: ABB Oy Device name: REM620 Highest DNP level supported: Device function: For requests: Level 2+ ○...
  • Page 70 Only non-time-tagged ○ Binary input change with relative time ● Configurable to send one or the other ● Configurable Sends unsolicited responses: Sends static data in unsolicited responses: ● Never ● Never Table continues on next page REM620 Point List Manual...
  • Page 71: Dnp3 Implementation Table

    (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07 or 08 are responded with qualifiers 00 or 01. Requests sent with qualifiers 17 or 28 are responded with qualifiers 17 or 28. For change-event objects, qualifiers 17 or 28 are always responded. REM620 Point List Manual...
  • Page 72 17, 28 (index) 32-bit 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) analog 06 (no range, or all) 17, 28 (index) input 07, 08 (limited qty) 17, 28 (index) Table continues on next page REM620 Point List Manual...
  • Page 73 Time and 129 (response) 07 (limited qty) date CTO 130 (unsol. resp) (qty = 1) Unsynchro 129 (response) 07 (limited qty) nized time 130 (unsol. resp) (qty = 1) and date Table continues on next page REM620 Point List Manual...
  • Page 74 17 or 28 are always responded.) 3) Writes of internal indications are only supported for index 7 (Restart IIN1-7) 4) Cold and warm restarts return an application layer acknowledge, but no restart action is taken. REM620 Point List Manual...
  • Page 75: Section 4 Glossary

    International Electrotechnical Commission IEC 61850 International standard for substation communication and modeling Intelligent electronic device IET600 Integrated Engineering Toolbox in PCM600 LHMI Local human-machine interface PCM600 Protection and Control IED Manager Select-before-operate WHMI Web human-machine interface REM620 Point List Manual...
  • Page 80 Contact us ABB Oy Medium Voltage Products, Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation...