Correct arrangement of multiple mono-bloc devices with representation of the air flow
direction
5.2.3.3 Securing the mono-bloc unit
The mono-bloc unit must be mounted on a flat, horizontal and solid surface. Besides the weight of
the device, the weight of the water must also be taken into account. The unit is to be mounted with
four M12 anchor bolts, each having a tensile force of more than 15,000 N.
Minimum requirements for anchoring the mono-bloc unit on the ground by means of a
foundation (A and B) or directly in the floor plate (C)
4
≥ 60
1
A Front view: Anchoring by means of foundation
1 Ground
2 Gravel filling
3 Strip foundation
4 Anchor bolts
5 Drain pipes
Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Wrong
980
775
A
60 mm
4
2
1
×100
3
200
1
1 Minimum distance: 100 mm
B
980
775
C
3
300 mm
3
All dimensions in mm
5
4
×100
2
Note: Schematic figure for explanation purposes
≥ 60
only.
B Top view
C Detailed view: Anchoring in the floor plate
3 Strip foundation
4 Anchor bolts
Planning
Correct
1
4
200
3
5
2
111