Building Scenario
External Components
(1) Outdoor air intake vent (end)
(2) Indoor air supply vent (end)
(3) Maintenance door
(4) Maintenance door
(5) Electric control box
(6) Outdoor air exhaust vent
(end)
(7) Indoor air return vent (top)
(8) Outdoor air intake vent (side)
Internal Components
(1) Air filters
(2) Spray modules
(3) Heat exchanger cores
(4) Condenser
(5) Exhaust fan
(6) Evaporator
(7) Spray pump
(8) Air supply fans
(9) Compressor
(10) Compressor drive
(11) Water tank
(12) Fan drive
Item
Scenario
Power system
Net weight
Dimensions (W x D x H)
2
Preparations
2.1
Preparing Special Tools
Crane (lifting capacity ≥ 15 tons), moving dolly, and electric forklift (including long arms).
2.2
Preparing Materials
FusionCol8000-E240
FDC scenario
380–415 V AC, three-phase, 50 Hz/60 Hz
11,000 kg
2438 mm x 6058 mm x 4150 mm
Building scenario
5000 kg
2438 mm x 4700 mm x 3600 mm
2