E-50
SICAM Q80 7KG8080
Evaluations / Standards
Voltage quality as per EN 50160
Data search and data comparison
across multiple measurements
IEC 61000-4-30 Ed.2 measurement accuracy and range
The accuracy and range specifications matches the IEC 61000-4-30 Ed.2 standard.
Parameter
Frequency
Magnitude of supply
Flicker
Dips and Swells
Interruptions
Unbalance
Voltage Harmonics
Mains signaling
voltage
Current
Active power
Reactive power
Apparent power
Power factor
Phase
Active energy
Reactive energy
Apparent energy
- The uncertainty for power and energy pertain to the apparent power or energy measurement values, respectively.
*U
= Operating voltage
nom
Power Quality Recorder SICAM Q80 7KG8080, Operating instruction
E50417-B1074-C419-A2, Release 12.01.2015
Uncertainty
10 mHz
0.1 %
5 %
0.2 %
-
0.15 %
5 % U
(U
>1 %)*
harm
harm
0,05 % U
(U
nom
harm
5 % U
(U
>3 %)
sgn
sgn
0,15 % U
(1 %< U
nom
sgn
±0.1 %
±0,2 %
±0,1 %
±0,4 %
±1°
±0,5 %
U
= Amplitude of the harmonics (RMS values)
,
harm
IEC 61000-4-30 Ed.2 class A compliant for the following:
- Frequency
- Magnitude of Supply Voltage
- Flicker
- Voltage Dips, Swells, Interruptions
- Unbalance
- Harmonics, Interharmonics
- Mains Signaling
- Time clock uncertainty
- Flagging
IEC 61000-4-15
IEC 61000-4-7
Power calculation as per DIN 40110-1 and –2 and IEEE
1459
Measuring Range
40 Hz to 57,5 Hz
50 Hz to 69 Hz
10 % to 200 %
0.2 to 10 Pst
-
-
0.5 % to 5 %
-
<1 %)
0 % to 9 %
<3 %)
Influence Quantity
Range
40 Hz to 57,5 Hz
50 Hz to 69 Hz
10% to 200 %
0 to 20 Pst
0 % to 5 %
0 % to 9 %
10 .. 130 % of input range
U,I > 10 %..max input range
U,I > 10 %..max input range
40 Hz bis 2.5 kHz
U,I > 10 %..max input range
-
-
-

Advertisement